GRID PRODUCTS Circuit Breakers
March 16, 2012 City of Ocala Resource Management th 1805 NE 30 Avenue Building “400”-Gate 1 Ocala, FL 34470 Attn: Ms. Jane Hurley RE: ITB 12-037 / USC Ref. No.: FL-USC-12449/1 Dear Ms. Hurley, Thank you for your interest in ALSTOM for your Power Circuit Breaker needs. We have received your inquiry and are pleased to submit the following proposal in accordance with your specification and with the noted comments and clarifications. We are proposing our DT1-72.5 F1 FK which is part of the ALSTOM family of circuit breakers. ALSTOM Grid is extremely interested in
continuing a successful business relationship with City Of Ocala. ALSTOM is proposing similar breakers that were provided under City Of Ocala PO’s 72284-72285-72286-72287-72288 and ALSTOM Order’s No CX05066-CX05067-CX05068-CX05069CX05070 respectively. To further demonstrate our commitment, ALSTOM will provide (1) complementary trip coil, (1) close coil and (1) motor with receipt of an order. These coils and motors can be used for any of the circuit breakers that were purchased in the past. ALSTOM is a leading manufacturer of high voltage circuit breakers and circuit switchers with R&D and manufacturing facilities located in Charleroi, Pennsylvania. Our facility is an ALSTOM Center of Excellence for research and development, testing, and manufacturing of dead tank circuit breakers for worldwide distribution and is certified to ISO9001-2008, ISO1400-2004 and OHSAS18001-2007. Our Charleroi, PA campus includes a fully functional research & development facility with a staff of over 20 engineers and technicians dedicated to product development. This local development team ensures that new products are designed to meet the rigorous demands of the US power system. The ALSTOM team also includes worldwide development with R&D centers in Kassel, and Villeurbanne, . We have currently delivered nearly 15,000 circuit breakers from this factory since 1993. The ALSTOM line of circuit breakers and circuit switchers are developed with a family approach. Common components such as mechanisms and interrupters are shared between the dead tank and circuit switcher products providing a reduction in cost of ownership. Furthermore, our breakers and switchers are tested to ensure significant Close-Open mechanical operations without maintenance. ALSTOM stands ready to serve you. Our uniquely qualified team includes industry leaders with decades of experience in the transmission and distribution world as well as the high voltage circuit breaker industry. The of the ALSTOM team are available at any time and are dedicated together with our Charleroi staff of nearly 200 employees to providing you best in industry service and . Regards, William J. Floder Regional Product Manager
[email protected] 724-483-7866 Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
Soman Varghese ALSTOM Area Manager
[email protected] 678-920-2709
Perry Webster Electric Sales Associates, Inc
[email protected] 954-385-3266
SECTION 00-400 PROPOSAL AND BID FORM
SECTION 00-400 PROPOSAL AND BID FORM Submit one (1) original and one CD (PDF format) electronic version.
ALSTOM Grid, Inc.
FY12-14 SUBSTATION UPGRADES 15KV AND 69KV BREAKERS OUS PROJECT NO. 01-07-01 OCALA, FLORIDA
One Power Lane
February 17, 2012
Charleroi, PA 15022
ITB 12-037
This is the Proposal of:
To:
City of Ocala Utility Services Ocala Utility Services 1805 Northeast 30th Avenue Bldg. 400, Gate 1 Ocala, Florida 34470
Attention:
Jane Hurley, Procurement Manager
1.
Proposal Pursuant to and in compliance with your Invitation to Bid dated February 17, 2012, the Instructions to Bidders and other documents relating thereto, the undersigned proposes to furnish and install the following equipment at the City of Ocala, Florida, at the prices listed below and within the times specified herein by the City of Ocala, and based on the description of Bid Item Numbers contained in Section 00-400.
FY-12 IMMEDIATE/DEFINITE REQUIREMENT:
Item
Qty
Unit of Measure
1
3
Each
1a
1
Lot
Description
Unit Price
Total Price
Circuit Breaker, High-Voltage, Outdoor, Reclosing, 69kV Class, 1200 Amp, 3-Pole, Single Throw, 60 Hertz, 350kV BIL, 3-Cycle, Symmetrical Interrupting Current 31.5 KA RMS, 4000 MVA Nominal Interrupting Capacity Class, Complete with required accessories. Complete requirements outlined in Sections 16-010 and 16-012.
$ 34,400.-
$ 103,200.-
Recommended Circuit Breaker Spare Parts Total
$ 635.-
$ 635.-
ALSTOM will provide (1) complementary Spare Parts Lot with receipt of an order.
8
SUBTOTAL
$ 103,835.-
SECTION 00-400 PROPOSAL AND BID FORM
Item
Qty
Unit of Measure
Description
Unit Price
2
5
Each
Circuit Breaker, High Voltage, Outdoor, 15kV Class, 1200 Amp, with Relaying. Complete with required accessories. Complete requirements outlined in Sections 16-010 and 16-014.
2a
1
Lot
Recommended Circuit Breaker Spare Parts Total.
Total Price
$
$
$
$ SUBTOTAL
$
TOTAL (1, 1a AND 2, 2a ABOVE): $ NO QUOTE Note: The above prices do not include Florida State Sales Tax, which is not applicable.
FY’13 REQUIREMENT (if funded in annual budget) Item
Qty
Unit of Measure
3
2
Each
3a
1
Lot
Description Circuit Breaker, High-Voltage, Outdoor, Reclosing, 69kV Class, 1200 Amp, 3-Pole, Single Throw, 60 Hertz, 350kV BIL, 3-Cycle, Symmetrical Interrupting Current 31.5 KA RMS, 4000 MVA Nominal Interrupting Capacity Class, Complete with required accessories. Complete requirements outlined in Sections 16-010 and 16-012. Recommended Circuit Breaker Spare Parts Total.
Will you hold your FY’12 bid price for FY’13 breakers?
X
Yes
______ No (indicate below any expected price escalation/de-escalation and the formula you would use to determine same)
9
SECTION 00-400 PROPOSAL AND BID FORM
FY’14 REQUIREMENT (if funded in annual budget) Item
Qty
Unit of Measure
4
2
Each
4a
1
Lot
Item
Qty
Unit of Measure
Description Circuit Breaker, High-Voltage, Outdoor, Reclosing, 69kV Class, 1200 Amp, 3-Pole, Single Throw, 60 Hertz, 350kV BIL, 3-Cycle, Symmetrical Interrupting Current 31.5 KA RMS, 4000 MVA Nominal Interrupting Capacity Class, Complete with required accessories. Complete requirements outlined in Sections 16-010 and 16-012. Recommended Circuit Breaker Spare Parts Total.
Description
5
7
Each
Circuit Breaker, High Voltage, Outdoor, 15kV Class, 1200 Amp, with Relaying. Complete with required accessories. Complete requirements outlined in Sections 16-010 and 16-014.
5a
1
Lot
Recommended Circuit Breaker Spare Parts Total.
NO QUOTE
Will you hold your FY’12 bid price for FY’14 breakers?
X
Yes
______ No (indicate below any expected price escalation/de-escalation and the formula you would use to determine same) Any FY’13 and/or FY’14 purchases must be mutually agreed upon by both the City of Ocala and awardee.
By submitting a bid, the bidder hereby certifies that the company submitting the bid is in compliance with all of the requirements of Department of Homeland Security’s E- System for the duration of the contract entered into between the City of Ocala and the Company or Organization OR will hire no employees for the term of the contract between the City of Ocala and the Company or Organization. Further information on E- can be found at the following website: http://www.uscis.gov/e-
10
SECTION 00-400 PROPOSAL AND BID FORM
2.
Discount Schedule A discount in the amount indicated will be allowed if payment is made within the number of days stated from date of invoice or date of delivery and acceptance, whichever is later. Item No.
3.
Description
Percent Discount
for Payment in Days
1.
Circuit Breaker, 69 KV, 1200 Amp
0% _____________
___________________
2.
Circuit Breaker, 15 KV, 1200 Amp
_____________ N/A
___________________ N/A
Manufacturer Item No.
Description
Manufacturer
1.
Circuit Breaker, 69 KV, 1200 Amp
2.
Circuit Breaker, 15 KV, 1200 Amp
ALSTOM Grid, Inc. N/A __________________________
If a bid is submitted for Items 1, Appendix 1 has been completed with pertinent information and is attached to this proposal. If a bid is submitted for Item 2, Appendix 2 has been completed with pertinent information and is attached to this proposal. Where spare parts are recommended, an itemized listing is attached to this Proposal, including description, part number, recommended quantity and price. 4.
Visa Accepted:
5.
List of Subcontractors and Major Suppliers
X NO _________
YES _________
The undersigned expressly agrees that: A. If awarded a contract as a result of this proposal, the subcontractor used in the prosecution of the work will be those listed below. OUS reserves the right to reject any subcontractor or specific employee, based on previous experience with said subcontractor or employee, without financial impact to OUS. Bidders are strongly encouraged to provide names of engineers and construction foremen in order to prevent rejection after the bid award.
11
SECTION 00-400 PROPOSAL AND BID FORM
B. The bidder represents that the subcontractors listed below are financially responsible and are qualified to do the work required. NAME OF SUBCONTRACTOR
CATEGORY
ADDRESS
Hauling
Brownlee Trucking Inc.
5035 Jefferson Avenue Avella, PA 15312
Advanced Freight Logistics
MAJOR SUPPLIERS
ALSTOM Grid, Inc.
6.
1245 S. Clev-Mass Rd Coplay, Ohio 44321
ADDRESS
One Power Lane-Charleroi, PA 15022
Equipment Delivery Schedule – FY’12 (Immediate Definite Requirement) Ocala Utility Services requires Delivery of equipment, as defined in Section 00-710, Paragraph 2, within the following dates:
Description
Delivery Required Not Earlier Than
Delivery Required Not Later Than
1.
Circuit Breaker, 69 KV, 1200 Amp
September 1, 2012
September 30, 2012
2.
Circuit Breaker, 15 KV, 1200 Amp
September 1, 2012
September 30, 2012
Item No.
12
SECTION 00-400 PROPOSAL AND BID FORM
The Bidder proposes to complete Delivery of Items, as listed below, including an allowance for review of shop drawings (see Section 00-810, Part 3, Paragraph D). The bidder understands proposed delivery times longer than stated above may be grounds for rejection of bid.
Item No.
Description
1.
Circuit Breaker 69 KV, 1200 Amp
2.
Circuit Breaker 15 KV, 1200Amp
Proposed Delivery Date
16-20 weeks ARO N/A
Delivery dates are based on a Conditional Notice of Award and Conditional Notice to Proceed of April 4, 2012. A Conditional Notice of Award of Contract and Conditional Notice to Proceed are conditioned only by the requirement that the Contractor shall deliver acceptable bond(s), proof(s) of insurance, and related documents, properly executed on behalf of the Contractor, and to otherwise demonstrate his fitness, willingness and ability to enter into the contract as described herein. Failure to issue Conditional Notice of Award, Conditional Notice to Proceed by the date indicated shall constitute basis for a day-for-day extension in the proposed delivery schedule. Conditional Notice of Award may or may not include the Conditional Notice to Proceed with the Contract. If the Conditional Notice to Proceed is separated from the Conditional Notice of Award, completion time shall be extended on a day-for-day basis to allow for elapsed time between Conditional Notice of Award and Conditional Notice to Proceed. 7.
Delivery to Be Made To Item No.
Description
1.
Three (3) Circuit Breakers 69 KV, 1200 Amp shall be delivered to the Utility Services Warehouse.
2.
Five (5) Circuit Breakers 15 KV, 1200 Amp shall be delivered to the Utility Services Warehouse
The Bidder agrees to deliver equipment to the Utility Services Warehouse at 1805 NE 30th Ave, Bldg 700, Gate #5, Ocala Florida 34470. Access requirements shall be established by on-site investigation by the Bidder. Delivery shall be completed between the hours of 7:30 a.m. and 12:00 noon, or 1:00 p.m. and 3:30 p.m. Local Time, Monday through Friday, but shall not be made on legal holidays and with a 48-hour notice prior to delivery. 8.
Bidder Agreement * The Bidder shall strike out the word(s) which do not apply.
“All items (are)* (are not)* quoted as per specification.” In the event the items covered by this quotation (including any modification or alternative) are not as specified, a full description is attached to the quotation describing the item (modification or alternative) on which the quotation is made, specifically noting exceptions to the specifications. The Bidder understands that failure to
13
March 16, 2012
FL-USC-12449/1
Page 6
Note: This offer is subject to mutually agreed upon & Conditions between City of Ocala and ALSTOM Grid, Inc. dated 02/27/2009. Please refer to the attached & Conditions.
Clarifications to Section 00-400: Paragraph 7.0 -No provisions are included in this proposal for Alstom to remove the equipment from the truck and place it onto the foundation. This will be the responsibility of others.
Clarifications to Section 00-710: Paragraph 17 - No provisions are included in this proposal for Alstom to remove the equipment from the truck and place it onto the foundation. This will be the responsibility of others.
Clarifications to the Breaker Specification’s 16-010 and 16-012: Note: This proposal is in reference to Sections 16-010 and 16-012 only, all other Sections to equipment does not apply.
Clarifications to the Breaker Specification’s 16-010: 1.05 -
Drawings and other documents will be submitted for approval four (4) to six (6) weeks after receipt of order.
3.01.B –
Alstom breakers are shipped on a low step-deck or flatbed truck with bushings assembled, main s open,
spring mechanism discharged and partially gas filled, thereby eliminating the need for a vacuum pump on site.
Clarifications to the Breaker Specification’s 16-012: 1.04.G -
Alstom’s proposed circuit breaker has Closing and Latching capability of 108kA.
2.02.M -
Operating temperature range of the proposed circuit breakers is -40C (Without Tank Heaters) to 50C.
2.02.O -
The circuit breaker will be provided with an external electrical trip push button with permissive control. The electrical push button is protected by the low gas lockout function and cannot be operated if the gas level should fall below safe operating levels. A mechanical trip lever is provided on each circuit breaker and located inside the mechanism enclosure.
2.03.A -
Alstom is proposing SF6 filled gray porcelain bushing without bushing studs. The breaker has a NEMA four (4) hole bushing terminal, made of aluminum and arranged in a horizontal plane. Stud connectors are not supplied.
2.04.C -
A latch check switch is not applicable to the proposed gas breakers since they do not incorporate a “collapsing” linkage and the trip latch restores itself fast enough to accomplish even a zero-time delay re-close. Therefore, it will not be provided.
2.05.B -
The circuit breaker will be supplied with 10 ‘a’ and 10 ‘b’ auxiliary s available for customer use. These s are factory set and are not field adjustable.
2.05.D -
The circuit breaker has one (1) common gas density monitoring system for the three (3) poles, located outside of the control housing, subject to ambient conditions. This pressure sensitive, temperature compensated SF6 gas density monitor has two (2) settings for the following functions for falling density: (1) alarm, (2) functional lockout. The settings are adjusted at the factory; therefore, they require no calibration and should not be adjusted in the field.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
SECTION 00-400 PROPOSAL AND BID FORM
INFORMATION FORM # 1 – ITB 12-037 References: 1.
Company & Name: Address: Phone No.:
Email:
Project Description:
Please refer to attached reference list immediately following this page. 2.
Company & Name: Address: Phone No.:
Email:
Project Description:
3.
Company & Name: Address: Phone No.:
Email:
Project Description:
4.
Company & Name: Address: Phone No.:
Email:
Project Description:
18
SECTION 00-400 PROPOSAL AND BID FORM
5.
Company & Name: Address: Phone No.:
Email:
Project Description:
Statement Regarding the Size, Capacity and Location of Facility(s):
Facility has 87,000 square feet. Alstom is currently expanding the facility to 100,000 square feet. Manufacturing capacity of 210 breakers per month. Facility is located in Charleroi, PA.
19
GRID PRODUCTS Circuit Breakers
S COMPANY
ADDRESS
City of Ocala
Mr. Pete Faulhaber Electric Substation Supervisor
Ocala, FL
[email protected]
City of Tallahassee (COT)
Mr. Greg Ozbun Supervisor T&D Operations
Tallahassee, FL greg.ozbun@talgov
850-891-5011
72.5kV 123kV 145kV 245kV
American Transmission Company (ATC)
Mr. Mike Anderson Principal Substation Design Engineer
Madison, WI
[email protected]
608-877-7147
72.5kV
Salt River Project
Mr. John Leech Senior Engineer
Tempe, AZ 86281-1027
[email protected]
602-236-3712
Westminster, CO
[email protected]
303-254-3409
Portland, OR
[email protected]
503-813-6883
72.5kV
Tri-State Generation & Transmission PacifiCorp
Ms. Irene Mulyar Electrical Engineering Manager Mr. Greg Lyons Engineering Manager
PHONE
352-351-6656
RATINGS 72.5kV
72.5kV 123kV 245kV 72.5kV 145kV 245kV
Northwestern Energy
Bill Endy Substation Superintendent
Billings, MT
[email protected] m
406-655-2577
72.5kV 145kV 245kV 550kV
Nebraska Public Power District
Donn Atchison T&D Asset Management Specialist
York, NE
[email protected]
402-362-7231
72.5kV 123kV
Portland General Electric
Brett Phillips
Portland, OR
[email protected]
LCRA
Sam Pulley
Austin Energy
Homer Portillo
ALSTOM Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
Austin, TX
[email protected] om
503-464-8047
512-369-4474 512-505-7133
72.5kV 123kV 245kV Switcher 145kV 72.5kV 145kV 145kV
SECTION 00-400 PROPOSAL AND BID FORM
STATEMENT OF "NO BID" IF YOU DO NOT INTEND TO BID ON THIS REQUIREMENT, PLEASE COMPLETE AND RETURN THIS FORM PRIOR TO DATE SHOWN FOR RECEIPT OF BIDS TO: CITY OF OCALA UTILITY SERVICES, PURCHASING DIVISION, 1805 NE 30TH AVENUE, BLDG 400, GATE 1, OCALA, FLORIDA 34470. WE, THE UNDERSIGNED, HAVE DECLINED TO BID ON YOUR BID NO. ITB 12-037 OPENING March 16, 2012, FOR FOR THE FOLLOWING REASON(S): SPECIFICATIONS ARE TOO "TIGHT", I.E., GEARED TOWARD ONE BRAND OR MANUFACTURER ONLY (PLEASE EXPLAIN REASON BELOW). INSUFFICIENT TIME TO RESPOND TO INVITATION TO BID. WE DO NOT OFFER THIS PRODUCT/S OR EQUIVALENT. OUR PRODUCT SCHEDULE WOULD NOT PERMIT US TO PERFORM. UNABLE TO MEET SPECIFICATIONS. UNABLE TO MEET BOND REQUIREMENTS. SPECIFICATIONS UNCLEAR (PLEASE EXPLAIN BELOW). COMPETITION RESTRICTED BY PRE-APPROVED CITY OF OCALA STANDARDS. OTHER (PLEASE SPECIFY BELOW). REMARKS:
WE UNDERSTAND THAT IF THIS "NO BID" LETTER IS NOT EXECUTED AND RETURNED, OUR NAME MAY BE DELETED FROM THE LIST OF QUALIFIED BIDDER'S FOR THE CITY OF OCALA FOR FUTURE PROJECTS OR COMMODITIES.
COMPANY NAME
ADDRESS
SIGNATURE AND TITLE TELEPHONE NUMBER
DATE
20
SECTION 00-400 PROPOSAL AND BID FORM
CITY OF OCALA - LOCAL VENDOR PREFERENCE AFFIDAVIT OF ELIGIBILITY This form is only to be submitted if you are eligible and requesting Local Vendor Preference This form is to be completed in its entirety by the prime vendor and submitted with your bid. Incomplete forms will be rejected for preference evaluation. In addition, each vendor shall submit a separate form for each major subcontractor the vendor proposes to employ. A major subcontractor is defined as a subcontractor whose subcontract constitutes five percent (5%) or more of the total contract price. In order for a vendor to be considered for local vendor preference, all major subcontractors must also qualify. Copy this form if additional forms are required and attach as submittals to each bid. 1. Legal Name of Firm:
N/A ___________________________________________________
Mailing Address: _______________________________ _______________________________ _______________________________
Physical Address (if different): _________________________________ _________________________________ _________________________________
2. Date your business was established in City of Ocala: _____________________ or Date your business was established in Marion County: _____________________ 3. Did you pay business or real property tax to either the City or the County for the most recent tax year?
Yes______
No______
4. Are you planning to employ any major subcontractors?
Yes______
No______
Under penalty of perjury, the undersigned states that the forgoing statements are true and correct. The undersigned also acknowledges that any person, firm, corporation or entity intentionally submitting false information in an attempt to qualify for local vendor preference shall be prohibited from bidding on City of Ocala products and services in accordance with -161 of the City of Ocala’s Purchasing and Procedures manual. Authorized Signature: ___________________________________
Date: _________________
Printed Name & Title: ___________________________________
Phone: ________________
State of: _____________________ County of: ___________________ Sworn to and subscribed before me this ________day of _____________________, 20___
Personally known _______ or Produced Identification ____________________________ (Specify Type of Identification) _____________________________ Signature of Notary
My Commission Expires ___________________
21
SECTION 00-400 PROPOSAL AND BID FORM APPENDIX 1 69KV – 1200 AMP
SECTION 00-400 PROPOSAL AND BID FORM - APPENDIX 1 - 69KV - 1200AMP SHEET 1 of 2 Information to be furnished by Circuit Breaker Manufacturer or Vendor with Bid
Manufacturer
ALSTOM Grid, Inc.
Location of Plant
Charleroi, PA
Model/Type/Design
DT1-72.5 FK / SF6 / Dead Tank
Rated Maximum voltage (KV)
72.5
Rated Voltage Range Factor (K)
1.0
Rated Low-Frequency Withstand (rms KV)
160
Rated Full-Wave Impulse Withstand (crest KV)
350
Continuous Current Rating (A)
1200
Closing and Latching Capability (A)
108
Short-Time Carrying Capability (A)
31,500
Original Manufacturer of Interrupter Unit
ALSTOM Grid, Inc.
Maximum Symmetrical Current Interrupting (KA) 31.5 Nominal Interrupting Capacity Class (MVA)
4,000
Rated Number of Interrupter Unit Operations
2,000
Opening Time (cycles)
1.5-1.9
Closing Time (cycles)
4.1-4.8
Minimum Reclosing Time
20 Cycles
Maximum Interrupting Time (cycles)
3
Minimum Control Voltage for Trip Operation
28-56V @ 48VDC
Minimum Control Voltage for Close Operation
36-56V @ 48VDC
22
SECTION 00-400 PROPOSAL AND BID FORM APPENDIX 1 69KV – 1200 AMP
SECTION 00-400 PROPOSAL AND BID FORM - APPENDIX 1 - 69KV - 1200AMP SHEET 2 of 2
Description of Operating Mechanism
Spring
Description of Stored Energy
Spring/Spring
Current Transformer Manufacturer
Narayan or Meramec
Number of Current Transformers /Accuracy Class (12) 1200:5 C400 Maximum CT Quantity for Space Available
(3) per bushing
Bushing Manufacturer
NGK or Argillon
Bushing Type /Designation (Composite bushings, if proposed, must be identified as an exception and Porcelain shall not be included in the base bid. External Creepage Distance, Phase to Ground (in) 74 External Striking Distance, Phase to Ground (in)
24.3
Phase Spacing (in)
37
Net Weight of Complete Circuit Breaker (lbs)
Approximately 3,800
Recommended Spare Parts: (use an additional sheet if needed) Description
Part Number
Cost
Close Coil
49.102.110-16
$105.-USD
Trip Coil
49.102.110-16
$105.-USD
Motor
1-417-294-G10
$425.-USD
Total: $ 635.-USD 23
SECTION 00-400 PROPOSAL AND BID FORM APPENDIX 2 15KV – 1200 AMP
SECTION 00-400 PROPOSAL AND BID FORM - APPENDIX 2 - 15KV - 1200AMP SHEET 1 of 2 Information to be furnished by Circuit Breaker Manufacturer or Vendor with Bid Manufacturer
No Quote
Location of Plant Model/Type/Design Rated Maximum Voltage (KV) Rated Voltage Range Factor (K) Rated Low-Frequency Withstand (rms KV) Rated Full-Wave Impulse Withstand (crest KV) Continuous Current Rating (A) Closing and Latching Capability (A) Short-Time Carrying Capability (A) Original Manufacturer of Interrupter Unit Rated Short-Circuit current Interrupting (A) Maximum Symmetrical Current Interrupting (A) Maximum Asymmetrical Current Interrupting (A) Percent of Rating for Specified Reclosing Cycle Rated Number of Interrupter Unit Operations Opening Time (cycles) Closing Time (cycles) Minimum Reclosing Time Maximum Interrupting Time (cycles) Minimum Control Voltage for Trip Operation Minimum Control Voltage for Close Operation
24
SECTION 00-400 PROPOSAL AND BID FORM APPENDIX 2 15KV – 1200 AMP
PROPOSAL AND BID FORM - APPENDIX 2 - 15KV - 1200AMP SHEET 2 of 2
Description of Operating Mechanism
No Quote
Description of Stored Energy
Current Transformer Manufacturer Number of Current Transformers /Accuracy Class Maximum CT Quantity for Space Available Bushing Manufacturer Bushing Type /Designation (Composite bushings, if proposed, must be identified as an exception and shall not be included in the base bid. External Creepage Distance, Phase to Ground (in) External Striking Distance, Phase to Ground (in) Phase Spacing (in) Relay Type / Model Net Weight of Complete Circuit Breaker (lbs) Recommended Spare Parts: (Use an additional sheet if needed) Description
Part Number
Cost:
Total: $ END OF SECTION 25
SECTION 00-430 BID BOND
SECTION 00-430 BID BOND KNOW ALL MEN BY THESE PRESENTS, that we, the undersigned, as Principal, and
as Surety, are hereby held and firmly bound
unto
as Owner in the penal sum of
for the payment of which, well and truly to be made, we hereby tly and severally bind ourselves, our heirs, executors, s, successors and assigns. Signed this
day of
, 20
.
The condition of the above obligation is such that whereas the Principal has submitted to a certain Bid, attached hereto and hereby made a part hereof to enter into a contract in writing, for the
NOW, THEREFORE, (a)
If said Bid shall be rejected, or in the alternate,
(b)
If said Bid shall be accepted and the Principal shall execute and deliver a contract in the form of the Construction Agreement attached hereto (properly completed in accordance with said Bid) and shall furnish a bond for his faithful performance of said contract and for the payment of all persons performing labor or furnishing materials in connection therewith, and shall in all other respects perform the agreement created by the acceptance of said Bid,
then this obligation shall be void, otherwise the same shall remain in force and effect; it being expressly understood and agreed that the liability of the Surety for any and all claims hereunder shall, in no event, exceed the penal amount of this obligation as herein stated. The Surety, for value received, hereby stipulates and agrees that the obligations of said Surety and its bond shall be in no way impaired or affected by an extension of the time within which the Owner may accept such Bid; and said Surety does hereby waive notice of any such extension.
26
SECTION 00-430 BID BOND
IN WITNESS WHEREOF, the Principal and the Surety have hereunto set their hands and seals, and such of them as are corporations have caused their corporate seals to be hereto affixed and these presents to be signed by their proper officers, the day and year first set forth above.
(L.S.) Principal
Surety
By
SEAL
END OF SECTION
27
SECTION 00-610 PERFORMANCE AND PAYMENT BOND
SECTION 00-610 PERFORMANCE AND PAYMENT BOND STATE OF FLORIDA COUNTY OF MARION CITY OF OCALA KNOW ALL MEN BY THESE PRESENTS, That as Principal, and a corporation organized and existing under the laws of the State of , having its home office in the City of and licensed to do business in the State of Florida, as Surety, are held and firmly bound unto the City of Ocala, Marion County, Florida, hereinafter called the City, in the penal sum of Dollars ($ ) for the payment of which well and s, successors and assigns, tly and severally, by these Presents: THE CONDITION OF THE OBLIGATION IS SUCH, that whereas the Principal on the day of , 20 , entered into a certain Contract with the City, hereto attached, for Contract entitled __________________________ - BID NO. _________, City of Ocala, Florida. NOW, THEREFORE, if the Principal shall well and truly perform and fulfill all the undertakings, covenants, , conditions, and agreements of said Contract and shall well and truly perform and fulfill all the undertakings, covenants, , conditions and agreements of any and all fully authorized modifications of said Contract that may hereafter be made, notice of which modifications to the Surety being hereby waived; AND FURTHERMORE, if the Principal shall promptly make payment to all claimants, as defined in Section 255.05 (1), Florida Statutes supplying Principal with labor, materials, or supplies, used directly or indirectly by Principal in the prosecution of the work provided for in said Contract that may hereafter be made, notice of which modifications to the Surety being hereby waived, then this obligation shall be void; otherwise it shall remain in full force and effect. As provided in Section 255.05(2), Florida Statutes, a claimant, except a laborer, who is not in privity with the Principal and who has not received payment for his labor, materials, or supplies shall, within forty-five (45) days after beginning to furnish labor, materials, or supplies for the prosecution of the work, furnish the Principal with a notice that he intends to look to this Bond for protection. A claimant who is not in privity with the Principal and who has not received payment for his labor, materials, or supplies shall, within ninety (90) days after performance of the labor or after complete delivery of the materials or supplies, deliver to the Principal and the surety written notice of the performance of the labor or delivery of the materials of supplies and of the nonpayment. No action for the labor, materials, or supplies may be instituted against the Principal or the Surety unless both notices have been given. No action shall be instituted against the Principal or the Surety on this Bond after one (1) year from the performance of the labor or completion of delivery of the materials or supplies. THIS BOND shall be security for the performance by the Principal and Surety of the following additional covenants and obligations, and the recitals and references herein contained shall constitute a part of this Bond and obligation: 1.
Each and every person, natural and artificial, for whose benefit this Bond has been executed, as disclosed by the text of this Bond and of said Contract, Specifications and Plans, and of said Agreement, and instruments attached together and made a part of the said Contract, shall have the same several rights of suit of action upon this bond as if he or they were the City herein specifically mentioned, and the obligations hereof shall be several as to the rights of said persons of the City.
2.
In each and every suit brought against the Principal and Surety upon this bond in which the Plaintiff shall be successful, there shall be assessed therein against the Principal and Surety herein, in favor of the Plaintiff therein, reasonable counsel fees and all costs and expenses incurred by the plaintiff which the Principal and surety hereby expressly agree to pay as part of the cost and expenses of such suit.
3.
In case of annulment of the Contract, as provided in the Specifications, there shall be assessed against the Principal and Surety herein, all expenses, including engineering and legal services, incident to collecting losses to the City under this Bond.
30
SECTION 00-610 PERFORMANCE AND PAYMENT BOND
IN WITNESS WHEREOF, the above bounded parties have executed this instrument under their several seals on the date indicated above, the name and corporate seals of each corporate party being hereto affixed and these Presents duly signed by its undersigned representatives, pursuant to authority of its governing body.
Principal – Sign name
Principal - Print name
By Pres., V. Pres., etc. – Sign name
Pres., V. Pres., etc. – Print name
Witnesses: Corporate Secretary – Sign name
Corporate Secretary - Print name
Surety – Sign name
Surety - Print name
Attest: (SEAL) (SEAL)
By NOTE: If both Principal and Surety are a corporation, the respective corporate seals should be affixed. Approved as to form and legality:
Patrick G. Gilligan, City Attorney
As the person authorized to sign the statement, I certify that this firm complies fully with the above requirements.
____________________________
Date: _________________
Vendor's Signature
END OF SECTION
31
March 16, 2012
FL-USC-12449/1
Page 2
Item 1 FY-12 Three (3) 72.5 kV Dead Tank Circuit Breakers according to ANSI/IEEE standards for outdoor installation with mechanical spring operating mechanisms including structures.
Type Rated nominal Voltage Rated maximum Voltage Frequency Rated continuous current Rated short-circuit current BIL Creep Distance / Material / Color Insulating medium Interrupting time High-speed auto-reclosure Current transformers Cabinet Enclosure Rating / Material Ambient temperature Seismic Rating Altitude Control Voltage Motor Voltage Alternate current circuit (lighting/heating):
DT1-72.5 F1 FK 69 kV 72.5 kV 60 Hz 1200 A 31.5 kA* 350 kV 74” / Porcelain / Gray SF6 3 cycles 3 phase, gang operated (12) 1200:5 MR C400, TRF 2.0 NEMA 3R / Painted Steel -30°C to +50°C without tank heaters Per IEEE / Low ≤ 3,300’ ASL 48 VDC or as Specified 240 VAC or as Specified 120/240 VAC
Price per Unit:
$34,400. - USD, FOB Jobsite, FL
Extended Price:
$103,200. - USD, FOB Jobsite, FL
Notes
* The X/R rating of the DT1-72.5 is 32 at 40kA. This breaker may be nameplated for up to 45kA interrupting current with a standard X/R=17. This provides significant performance margin and ensures that the circuit breaker will perform at the highest level with less maintenance. The DT1-72.5 is qualified to M2 class for mechanical endurance in accordance with IEC 62271-100. This rating qualifies the DT1-72.5 mechanically for 10,000 Close-Open operations without maintenance. The DT1-72.5 is qualified to C2 class for capacitor switching in accordance with IEC 62271-100. This rating qualifies the DT172.5 for switching of capacitive loads with very low probability of re-strike. The foundation layout dimensions of the DT1-72.5 are 40.5” x 40.5”, allowing for simplified installation for new construction as well as OCB replacement. State of the art proprietary bushing sealing system improves SF6 gas tightness. Porcelain Bushings are tested for high pollution environments using the salt-fog method. ALSTOM has delivered over 6,500 DT1-72.5 circuit breakers since 1993.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
March 16, 2012
FL-USC-12449/1
Page 3
Item 2 FY-13 Two (2) 72.5 kV Dead Tank Circuit Breakers according to ANSI/IEEE standards for outdoor installation with mechanical spring operating mechanisms including structures.
Type Rated nominal Voltage Rated maximum Voltage Frequency Rated continuous current Rated short-circuit current BIL Creep Distance / Material / Color Insulating medium Interrupting time High-speed auto-reclosure Current transformers Cabinet Enclosure Rating / Material Ambient temperature Seismic Rating Altitude Control Voltage Motor Voltage Alternate current circuit (lighting/heating):
DT1-72.5 F1 FK 69 kV 72.5 kV 60 Hz 1200 A 31.5 kA* 350 kV 74” / Porcelain / Gray SF6 3 cycles 3 phase, gang operated (12) 1200:5 MR C400, TRF 2.0 NEMA 3R / Painted Steel -30°C to +50°C without tank heaters Per IEEE / Low ≤ 3,300’ ASL 48 VDC or as Specified 240 VAC or as Specified 120/240 VAC
Price per Unit:
$34,400. - USD, FOB Jobsite, FL
Extended Price:
$68,800. - USD, FOB Jobsite, FL
Notes
* The X/R rating of the DT1-72.5 is 32 at 40kA. This breaker may be nameplated for up to 45kA interrupting current with a standard X/R=17. This provides significant performance margin and ensures that the circuit breaker will perform at the highest level with less maintenance. The DT1-72.5 is qualified to M2 class for mechanical endurance in accordance with IEC 62271-100. This rating qualifies the DT1-72.5 mechanically for 10,000 Close-Open operations without maintenance. The DT1-72.5 is qualified to C2 class for capacitor switching in accordance with IEC 62271-100. This rating qualifies the DT172.5 for switching of capacitive loads with very low probability of re-strike. The foundation layout dimensions of the DT1-72.5 are 40.5” x 40.5”, allowing for simplified installation for new construction as well as OCB replacement. State of the art proprietary bushing sealing system improves SF6 gas tightness. Porcelain Bushings are tested for high pollution environments using the salt-fog method. ALSTOM has delivered over 6,500 DT1-72.5 circuit breakers since 1993.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
March 16, 2012
FL-USC-12449/1
Page 4
Item 3 FY-14 Two (2) 72.5 kV Dead Tank Circuit Breakers according to ANSI/IEEE standards for outdoor installation with mechanical spring operating mechanisms including structures.
Type Rated nominal Voltage Rated maximum Voltage Frequency Rated continuous current Rated short-circuit current BIL Creep Distance / Material / Color Insulating medium Interrupting time High-speed auto-reclosure Current transformers Cabinet Enclosure Rating / Material Ambient temperature Seismic Rating Altitude Control Voltage Motor Voltage Alternate current circuit (lighting/heating):
DT1-72.5 F1 FK 69 kV 72.5 kV 60 Hz 1200 A 31.5 kA* 350 kV 74” / Porcelain / Gray SF6 3 cycles 3 phase, gang operated (12) 1200:5 MR C400, TRF 2.0 NEMA 3R / Painted Steel -30°C to +50°C without tank heaters Per IEEE / Low ≤ 3,300’ ASL 48 VDC or as Specified 240 VAC or as Specified 120/240 VAC
Price per Unit:
$34,400. - USD, FOB Jobsite, FL
Extended Price:
$68,800. - USD, FOB Jobsite, FL
Notes
* The X/R rating of the DT1-72.5 is 32 at 40kA. This breaker may be nameplated for up to 45kA interrupting current with a standard X/R=17. This provides significant performance margin and ensures that the circuit breaker will perform at the highest level with less maintenance. The DT1-72.5 is qualified to M2 class for mechanical endurance in accordance with IEC 62271-100. This rating qualifies the DT1-72.5 mechanically for 10,000 Close-Open operations without maintenance. The DT1-72.5 is qualified to C2 class for capacitor switching in accordance with IEC 62271-100. This rating qualifies the DT172.5 for switching of capacitive loads with very low probability of re-strike. The foundation layout dimensions of the DT1-72.5 are 40.5” x 40.5”, allowing for simplified installation for new construction as well as OCB replacement. State of the art proprietary bushing sealing system improves SF6 gas tightness. Porcelain Bushings are tested for high pollution environments using the salt-fog method. ALSTOM has delivered over 6,500 DT1-72.5 circuit breakers since 1993.
Item 4 Service:
Please refer to attached service quote for details.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
$5,757. - USD, FOB Jobsite, FL
March 16, 2012
FL-USC-12449/1
Page 5
Spare Parts We do not recommend any spare parts for start up or the first three (3) years of operation; however, for the purpose of comparison, we are giving the prices for the following spares: Item # a b c
Parts Description
DT1-72.5 F1 105.105.425.-
Trip coil Close coil Motor for spring charging
* A slow close device was required for oil type breakers with interrupters with adjustable wipe. On SF6 interrupters, the s never need adjusted during the life of the breaker. Therefore, the slow closing device does not add any functionality to the breaker. Prices of spare parts are valid only when they are ordered and delivered together with the circuit breaker. Spares ordered separately will be subject to shipping charges. We maintain all necessary spare parts in our stock. For emergency spares, we recommend items 1, 2 and 3. Spare parts ordered separately will be subject to shipping charges. Special Tools No special tools are necessary for installation or maintenance of the breakers. We do recommend, however, having one (1) of each of the following SF6 handling tools on site:
Handheld leak detector Gas regulator and fill hose set
480.- USD One (1) included per substation
The cost of these special tools, unless otherwise stated, is not included in the breaker pricing.
Erection and Commissioning Supervision *
Please refer to attached Service quote for details.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
March 16, 2012
FL-USC-12449/1
Page 6
Note: This offer is subject to mutually agreed upon & Conditions between City of Ocala and ALSTOM Grid, Inc. dated 02/27/2009. Please refer to the attached & Conditions.
Clarifications to Section 00-400: Paragraph 7.0 -No provisions are included in this proposal for Alstom to remove the equipment from the truck and place it onto the foundation. This will be the responsibility of others.
Clarifications to Section 00-710: Paragraph 17 - No provisions are included in this proposal for Alstom to remove the equipment from the truck and place it onto the foundation. This will be the responsibility of others.
Clarifications to the Breaker Specification’s 16-010 and 16-012: Note: This proposal is in reference to Sections 16-010 and 16-012 only, all other Sections to equipment do not apply.
Clarifications to the Breaker Specification’s 16-010: 1.05 -
Drawings and other documents will be submitted for approval four (4) to six (6) weeks after receipt of order.
3.01.B –
Alstom breakers are shipped on a low step-deck or flatbed truck with bushings assembled, main s open,
spring mechanism discharged and partially gas filled, thereby eliminating the need for a vacuum pump on site.
Clarifications to the Breaker Specification’s 16-012: 1.04.G -
Alstom’s proposed circuit breaker has Closing and Latching capability of 108kA.
2.02.M -
Operating temperature range of the proposed circuit breakers is -40C (Without Tank Heaters) to 50C.
2.02.O -
The circuit breaker will be provided with an external electrical trip push button with permissive control. The electrical push button is protected by the low gas lockout function and cannot be operated if the gas level should fall below safe operating levels. A mechanical trip lever is provided on each circuit breaker and located inside the mechanism enclosure.
2.03.A -
Alstom is proposing SF6 filled gray porcelain bushing without bushing studs. The breaker has a NEMA four (4) hole bushing terminal, made of aluminum and arranged in a horizontal plane. Stud connectors are not supplied.
2.04.C -
A latch check switch is not applicable to the proposed gas breakers since they do not incorporate a “collapsing” linkage and the trip latch restores itself fast enough to accomplish even a zero-time delay re-close. Therefore, it will not be provided.
2.05.B -
The circuit breaker will be supplied with 10 ‘a’ and 10 ‘b’ auxiliary s available for customer use. These s are factory set and are not field adjustable.
2.05.D -
The circuit breaker has one (1) common gas density monitoring system for the three (3) poles, located outside of the control housing, subject to ambient conditions. This pressure sensitive, temperature compensated SF6 gas density monitor has two (2) settings for the following functions for falling density: (1) alarm, (2) functional lockout. The settings are adjusted at the factory; therefore, they require no calibration and should not be adjusted in the field.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
March 16, 2012
FL-USC-12449/1
Page 7
General Conditions Validity
90 days after bid opening.
Delivery
Standard delivery on the DT1-72.5 F1 FK circuit breakers is sixteen (16) to twenty (20) weeks after receipt order, subject to prior factory loading and material availability.
Delivery Note
Delivery is based upon customer return of approved drawings in two (2) weeks. Drawings will be submitted for approval four (4) to six (6) weeks after receipt of order.
Shipping Point:
Charleroi, PA
of Delivery:
Pricing is firm in USD, FOB Jobsite, FL(INCO 2000), destination pre-paid and allowed. Unloading of the circuit breakers is to be provided by others.
Payment Conditions:
90 % NET 30 days after delivery and 10% NET after equipment is placed in service or 180 days from delivery whichever comes first.
Instruction Manuals:
One instruction book is shipped inside the control cabinet of the breaker. instruction book will ship within two weeks of breaker shipment.
Warranty:
Twelve (12) months after installation, not to exceed eighteen (18) months after delivery. Warranties exclude wear and tear associated with normal circuit breaker operation, circuit breakers used in special applications not covered by ANSI C37.06, and circuit breakers that have exceeded the maximum allowable cumulated current. Warranties are based on strict accordance with the maintenance instructions found in the breaker manual.
Sales Tax:
This offer does not include any sales tax (state, federal or local).
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
Remaining
March 16, 2012
FL-USC-12449/1
Page 8
Policy for Changes, Delay, and Cancellation Changes All requests for equipment changes or additions to the quoted design upon return of approval drawings will be reviewed for impact to the quoted price and shipment date. Prices and shipment date may be significantly affected closer to the original production schedule and can be more severe for changes requested after the start of production. Upon request for change, ALSTOM will issue a quotation detailing the effect on price and/or shipment when applicable. Any change which affects price and/or shipment date (including applicable fees as described in Delays/Cancellation) must be acknowledged by written customer acceptance in the form of a change order before the change will be implemented. Delays Orders that are requested to be rescheduled within 2 weeks following receipt of order are not subject to charges for delay. However, to help defray labor and inventory carrying costs that may accrue if a delay is requested beyond 2 weeks from receipt of order, charges will be assessed in accordance with the following fee schedule. Any circuit breakers for which delays are requested 0 - 2 weeks before shipment will be invoiced as per the original delivery schedule. Schedule
Delay Charge (% of contract value)
20+ weeks before shipment
0%
16 – 20 weeks before shipment
5%
8 – 16 weeks before shipment
10%
4 – 8 weeks before shipment
15%
0 – 4 weeks before shipment
15% plus storage fees
Cancellation Orders that are cancelled within 2 weeks after receipt or order by ALSTOM in Charleroi, PA will not be subject to cancellation charges. Charges will be assessed in accordance with the following fee schedule. Schedule
Cancellation Charge (% of contract value)
0 – 2 weeks after receipt of order
0%
2 – 6 weeks after receipt of order
10%
8 – 14 weeks before shipment
40%
4 – 8 weeks before shipment
60%
0 – 4 weeks before shipment
100%
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
March 16, 2012
FL-USC-12449/1
Page 9
General Comments The circuit breakers offered belong to a family of switchgear highlighted by the following features:
Third generation SF6 interrupter with advanced thermal effect interrupter. Mechanical spring/spring operating mechanism. More than 30,000 circuit breakers/switchers on order or in service since 1989, worldwide.
A spring type operating mechanism is used to operate the circuit breakers. The stored energy in the springs is sufficient to perform one (1) O-CO operation without recharging. The tripping springs are automatically recharged after every C operation. Duty cycle is O-0.3s-CO-10s-CO as standard. The breakers have NEMA four (4) hole bushing terminals, made of aluminum and arranged in a horizontal plane and NEMA two (2) hole, stainless steel, grounding pads located on opposite legs of the structure. Anchor Bolts, HV Terminals and Ground Clamps to be provided by others. The circuit breakers will be supplied with the maximum number of auxiliary s available for customer use. These s are factory set and are not field inter-interchangeable or adjustable. The circuit breakers have one (1) common gas density monitoring system for the three (3) poles, located outside of the control housing, subject to ambient conditions. This pressure sensitive, temperature compensated SF6 gas density monitor has two (2) settings for the following functions for falling density: (1) alarm, (2) functional lockout. The settings are adjusted at the factory; therefore, they require no calibration and should not be adjusted in the field. The circuit breakers have a common gas piping system with a common fill valve located outside of the control cabinet, and selfsealing type isolation valves are provided on each tank to facilitate the removal of gas from a single tank In the event of a loss of supply to the motor, a hand crank is included with each breaker to manually charge the spring. The breakers will be shipped on a low step-deck or flatbed truck with bushings assembled and partially gas filled, thereby eliminating the need for a vacuum pump on site. On-site assembly consists of topping off with SF6 gas and mounting the lower legs of the structure. The proposed circuit breakers have been tested according to applicable ANSI/IEEE standards. Type tests have been performed previously on a similar unit. A set of routine tests, also according to ANSI/IEEE standards, will be conducted on the circuit breakers prior to shipment from our factory in Charleroi, PA. A repetition of any of these tests or the inclusion of a test or testing procedure not covered in these standards or on our Routine Testing Report are not included in the price of the circuit breakers. The cost of routine equipment testing at our facility is included in the breaker pricing. All other costs (i.e. travel, lodging, and meal expenses) associated with witness testing are not included.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
March 16, 2012
FL-USC-12449/1
Key Features of the Circuit Breakers Circuit Breaker
Interrupter tanks are high strength, single piece cast aluminum
Suitable for three (3) phase auto-reclosing
SF6 gas for the first filling is included in this item
SF6 density monitor with color scale
SF6 loss <0.5 % per year
Operating Mechanism
Anti-pumping device
Anti-condensation heater
Two (2) independent trip coils, one (1) closing coil
Local mechanical C/O-operation
Aluminum access plate for conduit entrance
Removable door of housing with provisions for padlocks
Breaker position and spring charge indicators included
Bushing Current Transformers (BCT’s)
Each core of each single-phase current transformer is magnetically independent.
Costs associated with the type testing of the BCT’s are not included in the breaker pricing.
Actual tap arrangements are to be re-confirmed by td at time of order placement.
Thermal Rating factor ≥ 2.0
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
Page 10
One Power Lane Charleroi, PA 15022 Phone: 724-489-8133 Fax: 724-483-7771 www.alstom.com
SERVICE QUOTATION
Project City of Ocala Customer:
City of Ocala
Customer Ref:
DT1-07
Attention:
William Floder
Quote Number:
ECQ-0021
Telephone:
Alstom Grid Ref: DT1-07
Fax:
Quoted By:
Ray Henderson
e-mail:
Quote Date:
3/12/2012
Delivery:
4 to 6 weeks advance notice required for scheduling purposes. This quotation is for budgetary Purposes only. Only One Mobilization and Demobilization is included in this quote. Pricing in based per the delivery Schedule 3 CBRs in 2012 only. The 3 Circuit Breakers must be installed on its foundation, Grounded and AC and DC power terminated inside the control Cabinet prior to Alstom Arrival
Sixty (60) Days from date of quotation
Quotation Validity: and Conditions:
Net Thirty (30) Days from date of invoice
(See attached for Alstom Grid Services standard " and Conditions)
All prices included in this quotation are estimated. Invoicing will reflect actual cost. Additional time, including daily expenses, incurred due to delays outside the control of Alstom Grid, to include but not limited to weather, customer, material delivery delays, etc. will be charged up to eight hours per day at applicable rates. A handling charge will be added to all charges for traveling and living expenses. Scope of Work: Exterior Inspection Positive Pressure check Funtional Check of Controls, Relays and Alarms Timing of Main Measurement of Main Resistnace AREVA T&D Services Is ISO 9000 Certified. Cost Savings can be achieved if Technician Flys in the morning and start working in the afternoon.
Item
Description
Qty.
Unit
Unit Price
Extended Price
1
Airfare Pittsburgh PA to Orlando FL (R/T)
1
Each
$575.00
$575.00
2
Travel Expense
2
Day(s)
$150.00
$300.00
Completed By: Ray Henderson
Date:
Approved By:
3/12/2012
Date:
3
Travel Time Pittsburgh PA to Ocala FL (R/T)
2
Day(s)
$776.00
$1,552.00
4
Field Technician
2
Day(s)
$970.00
$1,940.00
5
Daily Living Expense
2
Day(s)
$350.00
$700.00
6
Shipping (Circuit Breaker Timer and 100amp C/R Test Set)(R/T)
1
Each
$690.00
$690.00
Total:
Please complete to approve and return to: ALSTOM Grid One Power Lane Charleroi, PA 15022 Tel: 724-489-8133 Fax: 724-483-7771 www.alstom.com
$5,757.00
Name: Signature:
Date:
Completed By: Ray Henderson
Date:
Approved By:
3/12/2012
Date:
QUALITY ASSURANCE
1
TS-00005
AREVA T&D Inc. Charleroi
Paint Finish Specification Rev. 4 Page 1/4
PURPOSE This specification outlines the paint finish requirements for fabrications used in the assembly of power circuit breakers. The specification applies to all fabrications made from material, such as ferrous material, which must be coated and/or otherwise protected in order to prevent corrosion caused by continuous environmental exposure. This specification also applies in cases where painting is performed for aesthetic purposes only and corrosion protection is not an issue (i.e. aluminum substrates).
SCOPE The specification applies to all AREVA T&D Inc. Manufacturing personnel, as well as all outside sources, responsible for the painting of material used in the assembly of power circuit breakers.
GENERAL The paint system defined by this specification is a two-part system, consisting of a hybrid epoxy primer and a polyester (TGIC) topcoat, which is applied via electrostatic spray. All resistance properties required by this specification are to be considered indicative of the system as a whole and do not necessarily reflect the performance of either coating as individually applied.
SPECIFICATION Coating Properties 1. Top Coat Coating Type: Thermoset Powder Coating Chemistry: Polyester (TGIC) Application Thickness: 2.0 to 3.0 mils (DFT) Pencil Hardness: 2H or better (ASTM D3363) Gloss: 80 ±5 units @ 60° (ASTM D523) Particle Size: 50 average 2.
Primer Coating Type: Coating Chemistry: Application Thickness: Pencil Hardness: Gloss: Particle Size:
Thermoset Powder Hybrid Epoxy 2.0 to 2.5 mils (DFT) 4H or better (ASTM D3363) 55-65 units @ 60° 50 average
Resistance properties (See Table 1)
Revision (Name, Date): R. Boyer 02-19-10
Reviewed (Name, Date): N. Davison, 02-19-10
UNCONTROLLED
File Name: TS-00005
QUALITY ASSURANCE Paint Finish Specification
AREVA T&D Inc. Charleroi
A.
TS-00005 Rev. 4 Page 2/4
Resistance properties (cont.)
Property Salt Fog Resistance
Environmental Cycling
Test Method ASTM B117 ("X" scribe)
ASTM 5894
QUV Accelerated Weathering
ASTM G53
Adhesion Impact Resistance
ASTM D3359 ASTM D2794
Abrasion Resistance Chemical Resistance
ASTM D4060 ASTM D3912
Rating
Specification
Creepage < 1/8" from scribe (ASTM D1654, Procedure A, Method 1)
Minimum 2000 hours
Body blisters (ASTM D1654, Procedure B, Table 2)
Rating of 7+
Pinhole Rust (ASTM D610) Creepage < 1/8" from scribe (ASTM D1654, Procedure A, Method 1)
Rating of 7+ Minimum 4 cycles (12 weeks)
Blister Rating (ASTM D714)
Rating of 7+
Pinhole Rust (ASTM D610) FS-40 bulb w cycle of 4 hours ultraviolet at 55°C followed by 4 hours condensation at 40°C. Cross-hatch method 60 in.-lb. direct impact (min.)
Rating of 7+ Minimum 500 hours w/ loss of gloss not exceeding 50% 5B Adhesion No chipping
20 in.-lb. reverse impact (min.) CS17 wheel, 1kg load Resistance to fumes, splash, or spillage (not immersion) for: • Fresh/Salt Water • Aliphatic Hydrocarbons • Oils: cutting, lubrication • Organic Acids • Glycol Ethers, Alcohol • Alkalies
Minimum 1000 cycles Moderately to Severely Resistant
(Table 1) C.
Visual Criteria 1. Color a. The following is to be furnished by the coating Supplier and is to accompany each unique lot of powder coat material: 1. Spectrophotometric data representative of the production lot a. Data is to be obtained through the use of a spectrophotometer using the L*a*b* scale under a D 65 (daylight) illuminant. b. Data should not represent a change in color > 1.00 ∆E from approved spectrophotometric values. 2. One sample representative of the production lot, coated at nominal mileage and displaying the following information: B. Visual Criteria (Cont.) • • • •
Color Supplier Product # Supplier Lot # Date
UNCONTROLLED
QUALITY ASSURANCE Paint Finish Specification
AREVA T&D Inc. Charleroi
•
TS-00005 Rev. 4 Page 3/4
Mileage c.
2.
For inspection purposes, the exactness of the coating's color will be verified through: 1. Comparison to known spectrophotometric values (not to exceed a deviation of 1.00 ∆E) Visual comparison of the sample to an approved master * kept on file in the Quality Assurance department. (Ref. Section E "Approval of New Color Masters") (*NOTE: The "master " is a which is felt to most closely reflect a coating's true color as agreed upon by the coating Supplier and Customer. This will serve as the standard against which all production lots will be judged for conformity of color.) c. In the event that a disparity is found to exist between spectrophotometric data provided by the Supplier and the color as observed during visual inspection, AREVA will default to using visual criteria in dispositioning the production lot. d. AREVA T&D Quality Assurance will retain all sample s for the period of two (2) years as a point of reference (in the event that a quality related issue should arise).
.
General Appearance a. b.
During visual inspection, the sample provided by the coating Supplier will be also assessed for general appearance (i.e. levels of gloss, orange peel, pin-holing, etc.) Significant deviation in the general appearance of the production sample from the approved master may result in the rejection of the production lot.
C. Application 1.
Pretreatment a. Ferrous Substrates Substrate surface shall be pre-treated prior to coating application, using one of the two procedures described below: 1.
2.
Mechanical Blasting - Aluminum oxide with 1.5-2.5 mil profile, to be employed within 4 hours of painting. Any residue left by blast media shall be removed via solvent cleaning or compressed air discharge prior to painting. Care shall be taken to avoid distortion or localized hardening of substrate material. Automated Multi-Stage Wash Automated multi-stage wash system, typically including phosphate pre-treatment, reverse osmosis cleaning rinse, and alkaline coating preparation rinse, including automated monitoring of process parameters such as pH, temperature, acidity, alkalinity, and system pressures and temperatures. (Supplier may be required to demonstrate effectiveness of a specific system prior to approval by Areva.)
In either case, Supplier shall have sufficient inspection steps in place prior to substrate preparation to ensure that substrate material is completely free of any deposits such as tar, adhesives, or any substance that would be immune to routine surface preparation. In order to be approved for use with ferrous substrates, a powder coating must demonstrate the ability to meet all properties designated by Section B, Table1, when applied in conjunction with the pretreatment defined by this specification. b.
Aluminum Substrates
UNCONTROLLED
QUALITY ASSURANCE Paint Finish Specification
AREVA T&D Inc. Charleroi
TS-00005 Rev. 4 Page 4/4
1.
Aluminum spinnings Clean surface with solvent prior to painting to remove any grease, dirt, oils, etc. 2. Cast Aluminum Clean surface with solvent prior to painting to remove any grease, dirt, oils, etc. 3. Wrought or Rolled aluminum Mechanically abrade surface and clean with solvent to remove any residue before painting. 3. In order to be approved for use with aluminum substrates, a powder coating must demonstrate the ability to meet all properties designated by Section B, Table 1, with the exclusion of "Salt Fog Resistance" and "Environmental Cycling" when applied in conjunction with the pretreatment defined by this specification 2. Application of Coating a. All powder coating is to be applied via electrostatic spray. b. The is to defer to the coating Supplier "Product Data Sheet" for product specifics such as specific gravity, bake cycle, cure temperatures, etc.). D. Approval of New Color Masters 1. Master s used for visual reference will be retained for the period of two (2) years. After the period of 2 years, due to degradation of color over time, a new master standard must be approved for use. At this time, the Supplier will submit a new for approval. To qualify as a replacement for a "color master", this new must exhibit a change in color no greater than .2 ∆E from the original master standard when measured using a spectrophotometer. 2. First-time color matches for all new coating Suppliers (existing colors) must exhibit a change in color no greater than .2 ∆E from an already approved color master. 3. Spectrophotometric data and sample s for all new colors must be submitted to AREVA T&D Inc. for final approval of the color match. All color masters used by the coating Supplier for inspection purposes must also be approved by AREVA. E. Formulation Changes 1. AREVA T&D Inc. reserves the right to request the coating Supplier to provide the specific formulation for a given powder coating at any time. 2. Under no circumstances are changes to be made by the coating Supplier to the original approved formulation of a powder coating purchased by AREVA unless previously approved by AREVA. F.
Touch-Up Touch-up of nicks, scratches and other imperfections is to be performed per AREVA specification TS-00006.
UNCONTROLLED
Alstom Grid Reference List High Voltage Circuit Breakers: Charleroi, PA Model: *DT1-72.5 FK Country
State End
Australia ALINTA
Aurora Energy - TPA Ballarat GoldFields Elsworth St Sub BHP Billiton Comalco Aluminum Ltd. Endeavor Energy (formerly Integral Energy) Ergon Energy ETSA Power
ETSA Utilities Integral Energy
Jemena
Jounama Hydro Power Station PowerCor
RailCorp RIO TINTO Aluminum Bell Bay LTD Singapore Power International Powernet
SP AusNet
Friday, March 09, 2012
Year Type kV 2006 2005 2006 2008 2007 2007 2005 2007 2006 2007 2011 2009 2011 2005 2006 2007 2008 2009 2010 2011 2012 2005 2006 2007 2008 2009 2010 2011 2009 2010 2012 2006 2006 2007 2008 2009 2010 2011 2011 2011 2009 2011 2006 2007 2008 2006
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 66 72.5 72.5 72.5 72.5 72.5 66 72.5 66 72.5 66 72.5 66 72.5 72.5 72.5 72.5 72.5
Total 9 2 4 1 2 1 7 1 1 1 9 1 15 4 18 14 17 38 23 32 1 11 6 13 8 15 29 1 9 2 1 1 3 5 4 7 9 8 3 2 1 1 2 26 3 7
Page 1 of 15
Country Australia
State End Transgrid United Energy Distribution Western Power
Bahrain Belize
Japan AE Power Belize Electric Limited
Brazil
Anglo American Companhia Paulista de Forca e Luz Brunei Methanol Company Sdn Bhd Department of Electrical Services DeS
Brunei
Canada
Alliance Pipeline Inc Arno Electric LTEE ATCO ATCO Electric BBA BC Hydro British Columbia Transmission Corp
Canfor Plateau Mills Cape Breton Power LTD Cartier Wind Energy
Construction Energie Renouvelable Corner Brook Pulp and Paper Limited Rail CVRD INCO EECOL Electric INC Elite Engineering ENMAX EPCOR ERCO Worldwide Gibraltar Mines Ltd. High Time Industries Ltd. Husky Energy Hydro One Hydro Ottawa
Friday, March 09, 2012
Year Type kV 2007 2011 2011 2006 2010 2011 2006 2010 2008 2011 2008 2010 2008 2005 2006 2006 2006 2006 2005 2011 2008 2006 2010 2005 2009 2009 2009 2010 2010 2011 2011 2012 2005 2006 2005 2006 2007 2010 2005 2008 2009 2007 2006 2006 2008 2006 2007 2009 2008 2008 2006 2006 2010
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 36 72.5 72.5 72.5 72.5 72.5 72.5 72.5 34.5 34.5 66 69 72.5 72.5 38 72.5 72.5 72.5 72.5 25.8 27.5 72.5 27.5 72.5 27.5 72.5 72.5 72.5 72.5 38 34.5 34.5 72.5 72.5 72.5 36 69 72.5 72.5 72.5 72.5 75 69 72.5 72.5 72.5 72.5 72.5
Total 8 11 9 5 2 2 2 1 4 12 7 12 1 5 9 1 1 2 1 2 3 1 1 6 1 3 7 6 11 2 19 6 1 1 4 3 4 2 1 1 1 1 3 1 3 1 8 1 1 1 1 41 4
Page 2 of 15
Country Canada
State End Iron Ore Company Manitoba Hydro Maritime Electric Medicine Hat New Brunswick Power Newfoundland & Labrador Hydro
Newfoundland Power Nova Scotia Power NR Green Power Richmond Steel Recycling Ripley Windfarm Saskatchewan Power
Chile
Colombia Costa Rica Dominican Republic
Schneider Canada Services and Projects Suncor Terminal Services Inc. Thompson Creek Mining Ltd. - Endako Mines Trans Canada Pipelines Inc Trans Canada Power & Light (TL) Westpark Electric Ltd Westwood Electric Xstrata Nickel Sudbury Bechtel Compania Minera Dona Ines de Collahuasi Copelec Pacific Hydro Chile S.A. Carbones del Cerrejon ICE
CDEEE-ETDE Consorcio Energetico Punta Cana - Macao Duralon Factory EDENORTE ETED
Ecuador
Friday, March 09, 2012
Industria del Papel SIDO, S.A. Andec S.A. CATEG Consorcio Azulec-Tesca Electrica de Guayaquil EMELNORTE
Year Type kV 2004 2006 2009 2006 2006 2006 2007 2008 2009 2011 2005 2010 2007 2010 2006 2005 2006 2009 2009 2006 2008 2008 2008 2007 2007 2006 2009 2010 2011 2007 2011 2010 2011 2007 2006 2007 2009 2009 2011 2009 2008 2010 2006 2010 2011 2012 2009 2011 2010 2009 2011 2009 2010
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 75.6 72.5 72.5 72.5 72.5 79 72.5 72.5 72.5 69 72.5 44 69 72.5 46 23 72.5 72.5 72.5 72.5 72.5 34.5 72.5 72.5 72.5 72.5 72.5 69 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 69 72.5 72.5 72.5
Total 1 1 2 4 1 5 1 1 2 1 2 30 2 1 2 9 9 12 1 1 1 1 2 2 2 1 2 9 2 1 4 1 2 5 2 1 1 2 5 1 7 3 6 1 4 6 1 1 3 1 4 5 6
Page 3 of 15
Country Ecuador
State End EMELNORTE Empresa Electrica Cotopaxi S.A. Empresa Electrica Quito SA Empresa Electrica Riobamba S.A. INPROEL
El Salvador
Nestle OMACONSA ETESAL
Ghana
Ghana Grid Company
Volta River Authority Guatemala
Agua Prieta Cementos Progreso S.A. Hidroelectrica Choloma S.A. INDE Ingenio El Pilar LIZTEX
Mina San Rafael
Guyana Iceland India Indonesia
Sugar Mill Gassa Guyana Power & Light, Inc. Fjardaal Aluminum Reduction Plant Areva T&D India (HVM) PT Chevron Pacific Indonesia
Jamaica
Jamaica Public Service Co.
Mexico
Hylsa Industrias GOSA SA Mexichem Tenaris Tamsa SVC VINITECK
New Zealand
Friday, March 09, 2012
Orion
Year Type kV 2011 2009 2011 2009 2010 2011 2011 2010 2005 2010 2011 2011 2011 2011 2007 2005 2006 2007 2008 2010 2011 2011 2010 2010 2011 2006 2007 2009 2011 2011 2011 2009 2005 2009 2006 2007 2009 2010 2005 2009 2010 2005 2006 2008 2008 2010 2011 2007 2011 2006 2007 2009 2010
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 69 72.5 69 72.5 72.5 72.5 72.5 46 46 72.5 34.5 38 72.5 34.5 72.5 72.5 34.5 34.5 72.5 69 72.5 72.5 69 72.5 72.5 72.5 72.5 69 72.5 72.5 72.5 72.5 72.5 48.3 44 44 44 69 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 66 66 72.5 72.5
Total 1 1 10 1 1 1 1 1 5 1 1 6 2 20 8 2 2 1 1 1 3 2 1 1 1 2 2 4 2 7 1 9 10 1 3 3 1 2 5 16 2 1 1 1 1 1 2 1 2 8 4 7 5
Page 4 of 15
Country New Zealand
State End Orion Transpower
Panama Autoridad del Canal de Panama COBRA ETESA Hidro Piedra Unión Fenosa EDEMET-EDECHI Peru
Southern Copper Xstrata Tintaya S.A.
Philippines
Avon River Power Holdings Corp. Cepalco
Clark Development Corp Cotabato Light Cotabato Light & Power Co. Davao Light & Power Co. HEDCOR Sibulan, Inc. MERALCO National Grid Corporation of the Philippines Nestle Petron PMG TRANSCO
VECO (Visayan Electric Company)
Puerto Rico
Friday, March 09, 2012
AES Graybar Int'l Jansen Ortho LLC McNeil
Year Type kV 2011 2012 2005 2006 2007 2009 2009 2010 2011 2012 2011 2008 2008 2010 2008 2010 2011 2008 2010 2009 2011 2005 2006 2007 2008 2007 2007 2009 2009 2010 2011 2010 2010 2011 2009 2008 2008 2010 2011 2011 2007 2005 2006 2006 2007 2007 2009 2010 2011 2011 2007 2009 2005
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 66 66 69 72.5 72.5 72.5 72.5 72.5 72.5 38 34.5 38 34.5 72.5 38 34.5 72.5 72.5 72.5 69 72.5 72.5 72.5 69 69 72.5 69 69 69 72.5 72.5 69 72.5 72.5 69 69 72.5 72.5 72.5 69 72.5 69 72.5 72.5 72.5 72.5 46 46 46 72.5
Total 16 4 2 4 7 3 1 4 2 3 2 1 1 2 2 1 1 2 2 1 1 1 2 6 8 1 1 1 1 2 1 6 1 1 2 2 1 4 3 1 1 8 6 9 5 4 11 16 13 3 2 1 1
Page 5 of 15
Country
State End
Puerto Rico
Merck Arecibo Puerto Rico Electric Power Authority
Veteran's Hospital Saudi Aramco Saudi Electricity Company Lung Ching Taiwan Railways
Saudi Arabia Taiwan
Trinidad and Tobago
Powergen
Turkey United Arab Emirates
Trinidad & Tobago Electric Co Yolbulan Steel Fuji
United Kingdom Venezuela
USA
Northern Power Grid Electricidad de Caracas PDVSA
AK AL
SINCOR Alaska Electric Light & Power Arab Electric Coop City of Florence Decatur Utilities Huntsville Utilities
AR
Redstone Arsenal City Light Water & Cable City Water & Light of Jonesboro Southwest Arkansas Electric Coop
AZ Continental Divide Electric Coop Navopache Electric Cooperative Salt River Project
Friday, March 09, 2012
Year Type kV 2007 2005 2005 2006 2007 2007 2008 2009 2010 2011 2011 2012 2011 2006 2012 2009 2009 2010 2011 2005 2008 2006 2009 2008 2011 2012 2009 2008 2009 2010 2010 2005 2011 2005 2008 2009 2006 2007 2008 2010 2008 2005 2010 2011 2012 2006 2006 2006 2006 2007 2008 2009 2010
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
48.3 46 48.3 46 38 46 46 46 46 46 72.5 72.5 72.5 69 72.5 72.5 72.5 72.5 72.5 72.5 72.5 66 69 38 69 72.5 72.5 72.5 72.5 72.5 34.5 38 72.5 48.3 72.5 72.5 48.3 48.3 48.3 72.5 48.3 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
Total 1 5 3 4 1 4 5 6 2 1 8 5 4 3 4 2 2 5 2 3 6 71 2 20 4 23 56 4 1 5 10 1 1 3 1 1 2 1 3 6 8 1 4 7 1 2 4 1 38 38 28 6 8
Page 6 of 15
Country
State End
USA
AZ
Salt River Project
CA
Southwest Transmission Cooperative City of Anaheim
City of Banning City of Burbank City of Colton City of Glendale City of Hercules City of Pasadena
City of Riverside DCO California Department of Water Resources Eurus Energy Modesto Irrigation District OptiSolar San Diego Gas & Electric SunPower CO
Black Hills Energy Colorado Springs Utilities
Fort Carson AFB
KC Electric Association Mountain Coal Company Southeast Colorado Power Assn Tri-State G&T
CT DE
Friday, March 09, 2012
Northeast Utilities Delaware Electric Cooperative Inc
Year Type kV 2011 2012 2012 2006 2007 2008 2009 2006 2009 2009 2005 2011 2005 2007 2008 2009 2010 2011 2012 2008 2010 2011 2007 2010 2010 2008 2006 2011 2005 2005 2006 2009 2006 2007 2008 2006 2007 2009 2010 2006 2009 2010 2005 2006 2006 2007 2008 2009 2010 2011 2010 2010 2011
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38 38 38 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38 48.3 72.5 38 72.5 38 38 38 38 38 38 72.5 72.5 72.5 72.5 72.5 48.3 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
Total 22 19 2 10 9 18 17 6 7 4 2 2 12 11 10 10 9 8 6 15 5 1 2 3 14 1 1 9 1 1 10 4 4 5 7 2 2 2 2 1 1 3 3 4 1 5 4 1 1 5 4 1 1
Page 7 of 15
Country
State End
USA
DE
Pepco Holdings, Inc.
FL City of Lakeland
City of Ocala
City of Vero Beach Covanta Hillsborough WTE Facility Jacksonville Electric Authority Kissimmee Utility Authority
Progress Energy - Florida Santee Cooper
Sumter Electric Tampa Electric Company
GA
GA Tech Georgia Transmission Corporation Municipal Electrical Authority of Georgia Southern Company Southern Company (Georgia Power)
GU
Guam Power Authority
HI
Chevron Hawaii Refinery Tesoro Kapolei Refinery Alliant Energy
IA
Cedar Falls Utilities Central Iowa Power Cooperative
Friday, March 09, 2012
Year Type kV 2008 2009 2010 2006 2005 2006 2007 2008 2009 2010 2005 2007 2009 2006 2008 2007 2005 2008 2006 2008 2011 2006 2009 2010 2011 2008 2010 2005 2006 2007 2008 2006 2010 2011 2010 2008 2010 2011 2008 2009 2010 2011 2007 2007 2005 2006 2007 2008 2009 2010 2011 2007 2007
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 48.3 72.5 72.5 38 38 38 38 48.3 48.3 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
Total 8 8 4 1 1 1 6 6 8 4 3 2 13 2 13 2 2 4 4 2 3 2 1 3 4 11 8 7 20 21 1 5 3 1 3 5 2 2 3 3 2 2 3 3 12 24 54 10 1 6 5 3 3
Page 8 of 15
Country
State End
USA
IA
Central Iowa Power Cooperative
Corn Belt Power Cooperative MidAmerican Energy Company
ID
Idaho National Laboratory Idaho Power
IL
Ameren
City of Naperville City of Springfield City of Sullivan Corn Belt Energy Corporation ExxonMobil Joliet Refinery IN
KS
Butler Rural Electric Coop City of Anderson HD Supply Utilities LTD. Peru Utilities Wabash Valley Power City of Belleville Goodyear
KY Bowling Green Municipal Electric Div Fort Campbell Glasgow Electric Plant Board Henderson Municipal P&L Louisville Gas and Electric Co Mayfield Electric & Water Systems Murray Electric System North American Stainless Owensboro Municipal Utilities Paducah Power System Warren RECC LA
Friday, March 09, 2012
Year Type kV 2008 2009 2010 2010 2006 2007 2008 2009 2010 2011 2012 2011 2006 2007 2008 2010 2011 2005 2006 2006 2007 2008 2009 2010 2005 2008 2005 2005 2007 2005 2006 2011 2006 2007 2009 2007 2008 2008 2005 2006 2007 2010 2010 2010 2005 2011 2008 2007 2010 2012 2009 2011 2006
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38 72.5 72.5 72.5 72.5 72.5 38 72.5 72.5 38 38 38 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38
Total 4 2 3 6 13 10 12 29 7 8 2 1 1 2 6 5 3 13 4 27 24 30 20 9 11 2 1 1 1 1 8 1 3 3 5 1 1 1 4 4 1 1 2 2 1 4 2 1 5 3 9 2 4
Page 9 of 15
Country
State End
USA
LA
Central Louisiana Electric Company
City of Natchitoches City of Ruston Dixie Electric hip Corp
Jefferson Daves Electric Coop Jefferson Davis Electric Coop Lafayette Utilities System Shintech Louisiana LLC
Washington-St. Tammany Elec Coop
MA MD
Washinton-St. Tammany Elec Coop Mass Development Finance Agency Easton Utilities Commission PEPCO Holdings Inc. Southern Maryland Electric Co
MI
MN
MO
City of Croswell Kimball Township Waste Management Consulting Engineers Group Elk River Municipal Utilities Minnesota Municipal Power Agency Minnesota Power
Northern States Power South Central Association Ameren
Central Electric
Friday, March 09, 2012
Year Type kV 2005 2006 2007 2007 2008 2009 2010 2011 2011 2006 2011 2005 2006 2008 2011 2005 2008 2011 2008 2009 2010 2009 2010 2011 2010 2007 2009 2006 2011 2012 2005 2006 2007 2009 2008 2011 2010 2006 2005 2011 2005 2007 2008 2008 2009 2011 2010 2009 2010 2011 2012 2008 2010
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
38 38 38 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 48.3 72.5 72.5 72.5 72.5 72.5 38 48.3 38 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
Total 2 10 4 5 6 9 4 11 1 2 7 1 4 18 15 5 1 7 1 8 4 9 2 25 4 2 2 5 1 13 3 4 7 5 1 1 1 6 1 1 2 4 1 3 3 1 4 1 25 45 10 2 5
Page 10 of 15
Country
State End
USA
MO
City of Fulton City of Independence
City Utilities of Springfield
Empire District Electric Kansas City Power & Light
Northeast Missouri Electric Power Coop MS
Central Electric Power Association Columbus Light & Water East Mississippi Electric Power Assoc. South Mississippi Electric Power Association
MT NC ND
Tallahatchie Valley Electric Power Northwestern Energy City of High Point Jones-Onslow Electric hip Corp. Central Power KEM Electric Cooperative Minnkota Power Mor Gran Sou Electric Coop Mountrail Williams Electric West Plains
NE City of Fremont Midwest Electric Cooperative Corp Nebraska Public Power District
NJ NM
NV
Friday, March 09, 2012
Western United Electric Coop Lehman Brothers Data Center Columbus Electric Cooperative Jemmez Mountain Electric Coop Kirtland Air Force Base Kit Carson Electric Coop Sandia National Laboratories Colorado River Commission
Year Type kV 2008 2007 2008 2009 2010 2005 2006 2007 2008 2010 2011 2010 2011 2006 2008 2010 2011 2007 2009 2006 2008 2010 2011 2009 2010 2011 2005 2006 2010 2011 2009 2006 2007 2008 2004 2012 2008 2008 2008 2006 2011 2010 2008 2011 2007 2006 2006 2006 2009 2008 2006 2005 2006
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 48.3 72.5 72.5 48.3 72.5 72.5 72.5 15.5 72.5 72.5 72.5 72.5 72.5 72.5 48.3 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38 72.5 72.5 72.5 72.5 48.3 72.5
Total 2 4 4 3 3 2 3 2 3 1 1 5 5 5 1 3 4 1 4 2 2 1 1 1 4 1 1 2 5 2 2 2 1 1 1 3 2 2 1 1 6 2 28 1 1 5 2 1 1 1 4 2 2
Page 11 of 15
Country
State End
USA
NY
Central Hudson Gas & Electric
Elemco Services Inc. National Grid Niagara Mohawk Power Corp
Noble Energy Orange & Rockland Plattsburgh Municipal Lighting Dept Village of Hamilton Village of Ilion Village of Sherburne OH ///// Unknown ///// American Electric Power
American Municipal Power ASA Bloomingburg, LLC City of Bryan City of Celina City of Hamilton City of Hudson City of Lebanon City of Wapakoneta City of Westerville Hancock-Wood Elec. Holmes Wayne RECC Marathon Ashland Petroleum LLC Republic Steel Sun Coke Company Tri-County Rural Electric Coop, Inc. Village of Minster Wright Patterson Air Force Base OK Grand River Dam Authority
NextEra Energy Northeast Oklahoma Electric Cooperative, Inc
Friday, March 09, 2012
Year Type kV 2009 2010 2012 2011 2007 2011 2006 2006 2006 2006 2006 2009 2006 2008 2005 2009 2010 2005 2010 2010 2010 2011 2012 2009 2006 2009 2006 2010 2010 2012 2008 2010 2007 2009 2010 2007 2009 2011 2011 2011 2008 2007 2012 2009 2010 2007 2010 2008 2009 2010 2011 2012 2009
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 15.5 25.8 48.3 72.5 38 72.5 48.3 48.3 48.3 48.3 72.5 25.8 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38 72.5 72.5 72.5 72.5 72.5 38 72.5 72.5 72.5 72.5 72.5 72.5
Total 3 5 3 3 1 1 1 1 2 4 4 5 1 1 1 4 1 1 1 2 38 78 14 1 1 3 1 1 3 1 1 2 3 4 1 4 2 1 1 1 1 1 1 4 1 2 1 20 40 13 20 1 1
Page 12 of 15
Country
State End
USA
OK
Stillwater Electric Utility Western Farmers Electric Coop
OR
Central Lincoln PUD
Pacificorp
Portland General Electric PA
Alliant Energy EPC Duquesne Light
Graymont Hoosac US Steel
SC
USX Corporation Progress Energy - Carolinas Progress Energy - Florida
Santee Cooper
SD
Black Hills Power & Light
TN Appalachian Electric Cooperative Athens Utilities Board City of Elizabethton Electric Department Clarksville Department of Electricity Cumberland EMC Dyersburg Electric System Gibson Electric hip Corperation Harriman Utility Board
Holy Springs Utility Department Johnson City Power Board
Friday, March 09, 2012
Year Type kV 2009 2008 2009 2010 2011 2007 2008 2010 2011 2009 2010 2011 2010 2011 2006 2005 2008 2008 2011 2007 2011 2008 2009 2010 2011 2006 2005 2005 2006 2007 2006 2009 2012 2007 2009 2011 2007 2009 2010 2008 2007 2010 2011 2006 2007 2007 2006 2007 2007 2008 2009 2006 2007
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38 38 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 48.3 72.5
Total 3 15 11 7 1 4 1 2 8 5 8 11 2 3 2 7 1 1 1 1 1 3 2 5 3 3 3 8 63 6 9 3 2 7 10 11 1 1 6 4 2 9 4 1 1 1 1 1 1 1 1 1 1
Page 13 of 15
Country
State End
USA
TN
Knoxville Utilities Board
La Follette Electric Dept LaFollette Utilities Board Lenoir City Utilities
Milan Department of Public Utilities Morristown Power System Murfreesboro Electric Department Nashville Electric Service Newport Utilities Board
TX
PSC Metals Tri-County EMC Tullahoma Utilities Board Bryan Texas Utilities CenterPoint Energy El Paso Electric Co Goodyear Tire & Rubber Co Greenville Electric Utility
UT
VA
WA WI
Lower Colorado River Authority TEPPCO City of Ephraim City of St. George Resolute Energy Corporation A & N Electric Cooperative Bristol Virginia Utilities Central Virginia Electric Cooperative City of Danville PPM Energy PUD No. 1 of Grays Harbor County American Transmission Company
Madison Gas & Electric
Friday, March 09, 2012
Year Type kV 2005 2007 2008 2009 2010 2011 2005 2008 2007 2009 2011 2008 2009 2011 2010 2007 2006 2009 2008 2010 2009 2006 2009 2006 2007 2009 2012 2007 2006 2008 2011 2010 2008 2010 2007 2011 2010 2006 2009 2012 2005 2005 2010 2005 2006 2007 2008 2009 2010 2011 2012 2006 2011
DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT DT
72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 48.3 72.5 72.5 72.5 72.5 72.5 69 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 38 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
Total 8 3 3 1 4 5 2 4 4 4 9 1 1 1 2 11 5 1 1 6 2 2 3 1 3 6 5 1 3 2 2 1 2 1 4 1 1 2 1 1 4 2 3 1 20 38 17 40 39 67 4 1 2
Page 14 of 15
Country
State End
USA
WI
WE Energies
WY
Wisconsin Public Service Corp Black Hills Power Pacificorp
Year Type kV 2006 2006 2012 2012 2009
DT DT DT DT DT
15.5 38 72.5 72.5 72.5
Total Items
Friday, March 09, 2012
Total 1 1 3 1 1
3998
Page 15 of 15
A
B
CIRCUIT BREAKER
C
D
INDICATOR LIGHT
STANDARD ANSI DESIGNATIONS CABINET LIGHT KNIFE SWITCH
1
COIL CHARGING MOTOR MAX CONT. PWR 4W
, NORMALLY CLOSED
PUSHBUTTON
, NORMALLY OPEN
RESISTOR/ HEATER
CONNECTOR TERMINAL BLOCK DENSITY MONITOR
AUXILIARY TERMINAL BLOCK
2 THERMOSTAT DOOR SWITCH
FUSE BLOCK
THERMAL OVERLOAD
FUSE BLOCK, SLUGGED
01CS BREAKER CONTROL SWITCH 23 THERMOSTAT 23X HEATER OR 27X LOSS OF POWER RELAY 30 ANNUNCIATOR 37 UNDERCURRENT ALARM 43L/R LOCAL / REMOTE TRANSFER SWITCH 49 MOTOR THERMAL OVERLOAD 52a,b BREAKER AUXILIARY SWITCH 52C CLOSE PUSHBUTTON 52CC BREAKER CLOSE COIL 52T TRIP PUSHBUTTON 52TC BREAKER TRIP COIL 52X CLOSING RELAY 52Y ANTIPUMP RELAY 52-MON BREAKER CONDITION MONITOR 63G SF6 PRESSURE / DENSITY GAUGE 63GX SF6 PRESSURE / DENSITY RELAY 69 PERMISSIVE CONTROL SWITCH 69-KI KEY INTERLOCK 74CC CLOSE COIL MONITOR 74TC TRIP COIL MONITOR 79X RECLOSE DELAY RELAY 83X MOTOR TRANSFER OR 88 MOTOR 88F MOTOR FAILURE ALARM 88LS MOTOR LIMIT SWITCH AIL AMBER INDICATOR LIGHT GIL GREEN INDICATOR LIGHT RIL RED INDICATOR LIGHT HTR HEATER
TOP VIEW OF CONTROL CABINET
1
CONTROL STATION
MECHANISM
DROP OUT
RELAY
CONTROL TERMINALS GROUND BAR
BCT TERMINALS
2
FUSED DISCONNECT TOGGLE SWITCH FUSED DISCONNECT, SLUGGED
FUSE PULLOUT
3
TRANSFORMER
3 FUSE PULLOUT, SLUGGED
28 SOURCE PIN NUMBER
ES:14 DESTINATION DEVICE DESIGNATION
ES:A1
DESTINATION PIN NUMBER
SECOND DESTINATION IF APPLICABLE
WIRING KEY
4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
LEGEND
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
1
OF
13
A
B
C
CLOSE CIRCUIT
1
D
TRIP CIRCUIT
EXTERNAL TRIP
SW1
1
1
2
1
TB1
TB1
FU1
2
1
3
15A
TB2
TB1 CUSTOMER REMOTE CLOSE
TB2 2
7R
RE
+
79X
1
52T1
RIL
TB2 2
TB2 8 1
CUSTOMER REMOTE TRIP
EE
TB3
SET RECLOSER AT NO LESS THAN 20 CYC.
TB2
OPTIONAL CUSTOMER LOCKOUT
9AR
1A
13
7 3
1
REMOTE OPEN INDICATION
GIL
LA1
7
69
TB9
TB9
109
100
MB1 13 88LS a
8
2
9R
SPARE TRIP COIL
MB1
13
88LS b
EA
TB2
63GX1
14
9
TB10
TB9
118
102
14 31
EA 63GX1
TB3
TB9
2
110
ES
21
52Y
EA
21
3W
63GX1 22 D
RE
+
TB9
79X
A1
C
11
ES TB10
14
112
SET TDPU AT 20 SEC
ES 2D 52Y
52-2 a
MA2
9
52-2 b
2
10
11 52CC 5.6 OHM MAX CONT. PWR 4W
52-3 b
13
MA3 52-3 b
11
AT1 1
MA1
ME
52-1 b
52TC2 5.6 OHM MAX CONT. PWR 4W
2 6D
AT1 1
TB7
2
80 A2
4D
TB9
AT1
6W
TB10
MD
119
52TC1 5.6 OHM MAX CONT. PWR 4W
AT1
3
TB10
108
117 4
3
MA1
52-1 a
3D
EA 63GX1
5W
4W
TB10 115
2W
10
A1
MA3
12
AT1
52-1 b
4
14
14
MC
9
MA1 13
3W
AT2
TB9 101
79
4 4D
AT1
2
A2
A2
88LS b
TB10 116
3
TB7
4W
1
A1
MB1
12
1D
TB10
MA2
5D
EGA 63G 47.9 psig
113 1W
3
3
88F 4
2
B1
EML
107
111
52Y
2
ADD JUMPER TO TRIP ON LOW SF6
AT2
3D
TB10
52-1 a
1
TB3
48 VDC
48 VDC
MA1 13
17
18
22
1
32
MA1 TB1
52-1 b
SW1
TB2 9A
2A
12
MB1
9
88LS b
A
RE
B
SET TDPU AT 20 CYC
79X
10
23
NOTES: 1) ALL DEVICES SHOWN IN DE-ENERGIZED POSITION 2) BREAKER SHOWN IN OPEN POSITION 3) SF6 SHOWN AT ZERO PRESSURE 4) CLOSING SPRING SHOWN IN CHARGED POSITION
TB10
FU1 TB1
114
15A 4
TB1 4
4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
CONTROL SCHEMATICS
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
2
OF
13
A
B
C
D
SPARE TERMINAL BLOCKS FOR CUSTOMER USE
1 MOTOR CIRCUIT
CUSTOMER ALARMS
FU2 20A/SLUG
TB1 1B
1
TB9
2
105 1
DT1 49 10-16A
5W 5
MB1 88LS a
6 2 3
4
TB9 103
2
1 2 T1 120VAC
AT2
1W 1D
5
1
EGA
TB9
6
106
6D
SPARE MOTOR LIMIT SWITCH
6W
TB4
TB4
31
32
TB4
TB4
34
35
2D
EGA
53
63G 52.2 psig
54
EA
61
63GX1
EA
EA
83
71
63GX1
63GX1 84
62
TB2
TB2
11
11A
B3
TB3
TB3
TB3
TB4
TB4
TB4
23
26
27
37
38
39
TB5
TB5
TB6
TB6
TB7
TB7
TB9
TB10
TB10
TB10
61
62
73
74
85
86
99
120
121
122
1
63GX1
SPARE AUXILIARY SWITCHES FOR CUSTOMER USE
LOW GAS LOCKOUT
TB4
TB3
20
22
LOW GAS ALARM
36 LOW GAS LOCKOUT
LOW GAS LOCKOUT
7
TB5
TB5
TB5
TB5
TB5
TB6
TB6
TB6
TB6
TB6
51
53
55
57
59
63
65
67
69
71
MA1 15 52-1 a
8
TB4 TB4
TB3
28
24
2
TB4
33
MA1 52-1 b
16
MA2 11
3
MA2
52-2 a
4
52-2 b
5
MA2 13
6
14
12
52-2 a
MA2 52-2 b
7
MA2 15
8
16
52-2 a
MA2 52-2 b
MA3
1
MA3
9
52-3 a
2
52-3 b
10
29
TB5
TB5
TB5
TB7
TB7
TB7
TB7
75
77
81
83
52
MB1
54
56
TB5
TB5
58
60
TB6 64
TB6 66
TB6 68
TB6
70
TB6
72
88LS a 21
DT1
12
14
49
DT1
22
EML 88F
11
3
MA3 52-3 a
4
2B
TB2
10A
EA
49 10-16A
3
TB2
10
72
4
4
TB2
B2
AT2
TB3
104
3
TB1
B1
AT2
M1
TB9
TB1
TB1
6
2W
T2
5
TB1
5
2
AT2
88 120VAC 1.6 kW
3
21
5D
MB1 88LS a
TB3
63G 47.9 psig
DT1 49 10-16A
TB3 19
TB1
5
MA3 52-3 a
6
7
MA3 52-3 a
15
MA3 52-3 b
16
8
6
TB7
FU2
TB3
20A/SLUG
25
MOTOR TROUBLE
76
TB4
TB7
TB7
78
82
3
TB7 84
30
MOTOR EXCESSIVE RUN TIME ALARM
NOTES: 1) ALL DEVICES SHOWN IN DE-ENERGIZED POSITION 2) BREAKER SHOWN IN OPEN POSITION 3) SF6 SHOWN AT ZERO PRESSURE 4) CLOSING SPRING SHOWN IN CHARGED POSITION
4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
CONTROL SCHEMATICS
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
3
OF
13
A
B
1
C
D
HEATERS
1
FU3 TBAC 40
15A 1
2
PHASE (HOT) WIRE 1
TH1 45-90 F
2 1W 1D 1
240 VAC
2 2D
HT1 H1 95 W 600 OHM
HT1
2W
TBAC PHASE (HOT) WIRE
41
3
3W
HT1
3D 3
H1
4
95 W 600 OHM
4D
HT1
4W
4
2
FU3
2
15A
1
2
FU4 20A 1
120 VAC 4
2
1 3 5
TBAC NEUTRAL WIRE
PL1 120 VAC
LS1
2
20 A
L1
1 - LINE 2 - NEUTRAL 3 - GND 4 - LOAD LINE 5 - LOAD NEUTRAL
L2
L1 GND
L1
42
3 GND
7D
3
EGA
7
TH1
63G
AT2 GND1
7W
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
NOTES: 1) ALL DEVICES SHOWN IN DE-ENERGIZED POSITION 2) BREAKER SHOWN IN OPEN POSITION 3) SF6 SHOWN AT ZERO PRESSURE 4) CLOSING SPRING SHOWN IN CHARGED POSITION
4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
CONTROL SCHEMATICS
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
4
OF
13
A
B
7 7
TB2:7
7R
LA1:1
8
EA:31
SW1:2,AT2:3W
9
TB9
0 1
99
100 MB1:13
DT1:4 1 0
101 MA1:13
DT1:5
2 0 1
3 0 1
102 MA2:9
4 0 1
MB1:1 103
5 0 1
104 MB1:4
6 0 1
106
105 MB1:5
RE:D MB1:6
RE:A 7 0 1
108
MB1:11 107
MA3:12
EML:A1
1 8 0 1
9 0 1
0 1
110
109 MB1:7
ES:13,RE:3
TB10
RE:C
ES:A1 1
2 1
113
112
MA1:1 111
MB1:14,MB1:8
TB2 TB2:7R
MA1:2
AT1:6W
2 1 9 3
B 2
AT1:1W
39
TB3:13
B2
8 3
B 1
ES:A2,TB1:4
38
7 3
6
3 1
B1
6 3
4 1
37
5 3
5
114
EA:84
6
4 3
4
MB1:10,MA1:12
EA:71
36
3
TB2:9A
EA:83
35
5
EA:32
34
4
5 1
3
6 1
FU1:2 TB10:114,RE:B
3
7 1
EA:54
2 3
B 2
116
EA:61
33
B 1
MA1:3
32
2B
MA1:11 115
1B
8 1
FU2:1 FU2:3
117
1 3
AT1:4W
0 3
9 1
EA:53
9 2
MA2:1 118
EML:11
31
A 2
0 2 1
EML:14
30
2
A 1
119
29
1A 2A
1 2
2
SW1:1,TB1:1
120
EML:12
8 2
121
28
SW1:3,TB1:2
TB1:2A,FU1:3
1
TB4
1 1
D
TERMINAL BLOCK WIRING
TB1
122
TB1:1A,FU1:1
C
TB2:8
R 7
8
TB2:7
9 9
EA:31,EE:2
9R
TB10:117,TB7:80
9A
R 9
A 9
EA:13,EE:1 9AR MA1:8
MA1:7
2
TB5
MA1:15
51
5 1
MA1:16
52
5 2
MA2:3
5 3
53
5 4
54
MA2:4 56
55
MA2:11
5
MA2:12
5 6
MA2:5
57
5 7
58
5 8
59
5 9
60
6 0
6 1
61
62
6 2
TB6
MA2:6
MA2:13
MA2:14
63
MA2:7
6 3
MA2:8
6 4
64
MA2:15
6 5
65
MA2:16
66
MA3:1
6
67
6 7
MA3:2
6 8
6 9
70
68
MA3:9
69
MA3:10
7 0
71
7 1
72
7 2
7 3
7 4
73
74
MA3:3 75
TB7
MA3:4 7 5
76
MA3:5 7 6
MA3:6 7
77
MA3:13
78
MA3:14
7 8
MA3:7
79
7 9
MA3:8
8 0
80
MA3:15
81
8 1
82
MA3:16 8 4
8 5
8 6
85
A 1
B3
86
1
11A
8 2
2
8 3
11
83
0 1
A 0 1
84
A R 9
10 10A
TB2:9A,EA:A2
B 3
TB3 TB10:115
13
EA:14
17
EA:32
18
AT2:5W
19
AT2:6W
20
AT2:1W
21
AT2:2W
22
3 1
7 1
8 1
9 1
0 2
1 2
2
23 3 2
TBAC
DT1:21
24
DT1:22
25
40
FU3:1
26
41
FU3:3,FU4:1
27
42
PL1:2
4 2
5 2
6 2
7 2
GND1 1
2
3
4
5
6
7
8
9
10 11 12
3
3
13 14 15 16 17 18 19 20 21 22 23 24 1 TH1:GND 2 L1:GND,PL1:3 4 AT2:7W
NOTES: 1) ALL WIRING TO BE 12GA GRAY SIS VW1 2) ALL GROUND WIRING TO BE 12GA GREEN SIS VW1 3) WIRE MARKERS TO BE SHRINK-TYPE AND TO SHOW SAME-END/OPPOSITE-END DESIGNATION 4) WIRE LUGS ARE TO BE BURNDY TYPE INSULATED "YAEV" (EXCEPT FOR DEVICES THAT DO NOT ACCEPT RING-TYPE TERMINALS)
4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
WIRING DIAGRAM
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
5
OF
13
A
B
C
D
MECHANISM WIRING LS1 1 PL1:4 2 L1:L1
1
1
L1 EGA
L1 LS1:2 L2 PL1:5 GND GND1:2
L1
63G
1
3
1 2 3 4 5 6 7
5
GND
2
L2
7
2
4
52.2 psig
WATTAGE - 40 W
47.9 psig
6 47.9 psig
AT2:1D AT2:2D AT2:3D AT2:4D AT2:5D AT2:6D AT2:7D
1
STANDARD CABLE COLORS 1 - BLK 4 - ORA 7 - GRN 2 - RED 5 - WHT 3 - BLU 6 - WHT/BLK or BRN
MC 52CC 1
1 2
AT1:1D AT1:2D
2
MB1
COIL VOLTAGE - 48 VDC COIL RESISTANCE - 5.6 OHM
88LS
1
3
a
a
2
4
5
7
a
9
a 8
6
11
13
1 TB9:103 2 M1:T1 3 M1:T2 4 TB9:104 5 TB9:105 6 TB9:106 7 TB9:109 8 TB9:110
15
b
b
b
b
10
12
14
16
9 MA1:10 10 TB10:114 11 TB9:107 12 MA3:11 13 TB9:100 14 TB9:110
MA1 1
a 2
MA2 1
2
a
AT1 M1
88 T1
T1 MB1:2 T2 MB1:3
T2
MD 52TC1
MC:1 1D
1W TB10:113
MC:2 2D
2W MA1:9
MD:1 3D
3W MA1:4,MA1:14
MD:2 4D
4W TB10:117
ME:1 5D
5W MA2:2,MA2:10
ME:2 6D
6W TB10:119
1
ME 52TC2 AT1:3D AT1:4D
1
1 2
AT1:5D AT1:6D
2
MA3 2 COIL VOLTAGE - 48 VDC COIL RESISTANCE - 5.6 OHM
MOTOR VOLTAGE - 120VAC WATTAGE - 1.6 kW
EE
1 2
1
2 COIL VOLTAGE - 48 VDC COIL RESISTANCE - 5.6 OHM
a 2
52-1 3
5
a
a
4
7
a
9
11
13
15
b
b
b
b
6
8
10
12
14
16
5
7
9
11
13
15
b
b
b
b
1 TB10:111 2 TB10:112 3 TB10:116 4 AT1:3W 7 TB5:51 8 TB5:52 9 AT1:2W 10 MB1:9
11 12 13 14 15 16
TB10:115 TB10:114 TB9:101 AT1:3W TB5:53 TB5:54
1 2 3 4 5 6 7 8
TB10:118 AT1:5W TB5:55 TB5:56 TB5:59 TB5:60 TB6:65 TB6:66
9 10 11 12 13 14 15 16
TB9:102 AT1:5W TB5:57 TB5:58 TB6:63 TB6:64 TB6:67 TB6:68
1 2 3 4 5 6 7 8
TB6:69 TB6:70 TB7:75 TB7:76 TB7:77 TB7:78 TB7:81 TB7:82
9 TB6:71 10 TB6:72 11 MB1:12 12 TB9:108 13 TB7:79 14 TB7:80 15 TB7:83 16 TB7:84
52-2 3
a
a
4
a
6
8
10
12
14
16
5
7
9
11
13
15
2
52-3 3
a 4
a 6
a 8
b
b
b
b
10
12
14
16
52T1 1
3
2
4
1 2
TB2:9AR TB2:9R
5W
PL1
6D
5D
H1:4 4D
2
4
1
H1 1
3
2
4
1 2 3 4
HT1:1D HT1:2D HT1:3D HT1:4D
WATTAGE - 2X 95 W RESISTANCE - 2X 600 OHM
4
GFI 4
6W
3W TH1:1,FU3:2
1 TB2:8 2 ES:21
H1:1 1D
2
3
3 4W HT1:2W
69 1
H1:3 3D
LA1
1W TH1:2
COLOR - BLK
H1:2 2D
3
2W HT1:4W,FU3:4
HT1
1 2 3 4 5
FU4:2 TBAC:42 GND1:2 LS1:1 L1:L2
1 - LINE 2 - NEUTRAL 3 - GND 4 - LOAD LINE 5 5 - LOAD NEUTRAL VOLTAGE - 120 VAC AMP RATING -20 A 3
NOTES: 1) ALL WIRING TO BE 12GA GRAY SIS VW1 2) ALL GROUND WIRING TO BE 12GA GREEN SIS VW1 3) WIRE MARKERS TO BE SHRINK-TYPE AND TO SHOW SAME-END/OPPOSITE-END DESIGNATION 4) WIRE LUGS ARE TO BE BURNDY TYPE INSULATED "YAEV" (EXCEPT FOR DEVICES THAT DO NOT ACCEPT RING-TYPE TERMINALS)
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
WIRING DIAGRAM
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
6
OF
13
A
B
C
D
RELAY WIRING TH1 1
1
1 HT1:3W 2 HT1:1W GND GND1:1
1
GND 2 TEMP SETTING - 45-90 F
RE
79X
D +
4
2
A +
C
1
3
A B D C 2 3
TB9:108 TB1:4 EA:22,TB9:107 TB10:113 FU1:2 TB10:111
B
COIL VOLTAGE - 48VDC/48VAC COIL RESISTANCE - SOLID STATE
EA
ES
63GX1
A1 A1 A2 13 14 21 22 14 44 22 32 A2 31 32 53 83 61 71 53 54 61 62 54 84 62 72 71 72 COIL VOLTAGE - 48VDC 83 COIL RESISTANCE - 852 ohm 84 13
2
43
21
31
AT2:4W EML:A2,TB7:80 SW1:2,TB2:9AR TB3:17 ES:22 RE:D TB2:9,TB2:9R TB3:18,TB10:116 TB4:31 EA:62,TB4:33 TB4:32 EA:54 TB4:35 EA:84 TB4:34 EA:72,TB4:36
13
14
EML
52Y 43
44
21
22
31
32
A1 A1 A2 13 14 21 22 A2
ES:14,TB10:112 FU1:4,TB10:114 ES:21,TB10:111 ES:A1 ES:13,LA1:2 EA:21
12
11
COIL VOLTAGE - 48VDC COIL RESISTANCE - 852 ohm
DT1
88F 14
22
24
21
A1 TB9:110 B1 A2 SW1:4,EA:A2 12 TB4:28 11 TB4:30 14 TB4:29
A1
A2
COIL VOLTAGE - 48VDC COIL RESISTANCE - SOLID STATE
49
1
3
5
13
21
2
4
6
14
22
AMP RATING - 10-16A
1 2 3 4 5 6 21 22
FU2:2 DT1:3 DT1:2 TB9:103 TB9:104 FU2:4 TB3:24 TB3:25
2
AT2 FU1 1
SW1 3
1 TB1:1 2 RE:2,TB1:3 3 TB1:2 4 ES:A2
1
2
3
2
4
3
1 TB1:1A 2 EA:13,TB9:109 3 TB1:2A 4 EML:A2
FU2 1
3
1 TB1:1B 2 DT1:1 3 TB1:2B 4 DT1:6
1
FU4 3
1 TBAC:40 2 HT1:3W 3 TBAC:41 4 HT1:2W
1
1 TBAC:41 2 PL1:1
4
2
AMP RATING - 15A
FU3
4
2
AMP RATING - 20A/SLUG
4
TB3:21 1W
1D EGA:1
TB3:22 2W
2D EGA:2
TB9:109 3W
3D EGA:3
EA:A1 4W
4D EGA:4
TB3:19 5W
5D EGA:5
TB3:20 6W
6D EGA:6
GND1:4 7W
7D EGA:7
3
2
AMP RATING - 15A
AMP RATING - 20A
NOTES: 1) ALL WIRING TO BE 12GA GRAY SIS VW1 2) ALL GROUND WIRING TO BE 12GA GREEN SIS VW1 3) WIRE MARKERS TO BE SHRINK-TYPE AND TO SHOW SAME-END/OPPOSITE-END DESIGNATION 4) WIRE LUGS ARE TO BE BURNDY TYPE INSULATED "YAEV" (EXCEPT FOR DEVICES THAT DO NOT ACCEPT RING-TYPE TERMINALS)
4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
WIRING DIAGRAM
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
7
OF
13
A
B
C
D
1
1
TOP VIEW OF CONTROL CABINET CONTROL STATION
MANUFACTURING NOTES: 1) DEVICES TO BE MARKED WITH ENGRAVED PLASTIC TAGS. 2) DIN RAIL TO BE PER AREVA SPEC 1_415_881. 3) POSITION INDICATOR TAGS ATTACHED w/SCREWS 4) EDGE GUARD TO BE USED IN 9 PLACES AS SHOWN * AS WELL AS OTHER POINTS WHERE THE WIRE COMES IN WITH A METAL EDGE 5) FOR BURNDY TYPE INSULATED "YAEV" WIRE LUG SEE CONTRACT ORDER ENGINEER
MECHANISM
DROP OUT
RELAY EGA
CONTROL TERMINALS GROUND BAR BCT TERMINALS L1 LS1 L1 40 W
MECHANISM
LS1 TERMINAL BLOCK
MFR WIREWAY 2X2 - MOUNTED TO BACK OF MECH MFR WIREWAY 2X3
*
TH1
TB4
*
*
T H1
MFR WIREWAY 2X4
CUSTOMER WIREWAY 1.5X3 TB9
MFR WIREWAY 2X3 TB1
TB10
*
RELAY
ON "L" BKT LOWER EDGE
MFR WIREWAY 2X4
2X
1X
2Y
1Y
4X
3X
4Y
3Y
6X
5X
2
2
ES
EML
DT1
0 0 0 0 0 0 0
MD MD
M1
52TC1
* *
MA1
ME ME
MA1
52TC2
52-1
MA2
M1
*
88
MA2 52-2
MA3
52Y
63GX1
AT1 MA3
MFR WIREWAY 2X4
ES
MC 52CC
MB1 88LS
MFR WIREWAY 2X4
EA
MFR WIREWAY 1X3
MB1
MFR WIREWAY 1X3
RE 79X
EA
CUSTOMER WIREWAY 1X3
MFR WIREWAY 2X3
TB2
MC
MFR WIREWAY 1X3
RE
MFR WIREWAY 1X3
MFR WIREWAY 1.5X3
MFR WIREWAY 1.5X3
5Y
6Y
52-3 STOP
*
START
TB3 DT 1
EML
49
SW1
15A
30 AMP
FU2 FU2
MFR WIREWAY 1X3 FU3
20A/SLUG
FU4
FU3
FU4
15A
20A
TBAC
MFR WIREWAY 1.5X3
TB5
SW1
FU1
TB7
FU1
TB6
88F
*
AT1
AT2
3
AT2
3
H1
MFR WIREWAY 1X3
E-TRIP
MOUNTED THROUGH CABINET DOOR PUSH TO RESET
PL1
H1 PL1
GND1
2X 95 W
GFI
HT1 LOCKOUT
EE EE
HT 1
LA1
E-TRIP
RESET LA1
SEE PROCEDURE_0184 - (WIDE BOX) SEE PROCEDURE_0210 - (NARROW BOX) FOR INSTALLATION
MOUNTED THROUGH CABINET
4
MOUNTED TO ACCESS
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
LAYOUT
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
8
OF
13
A
1
2
B
C
ITEM 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 018 019 020 021 022 023
QTY 001 001 001 001 001 004 001 002 001 001 002 004 002 001 001 001 001 001 001 001 003 001 036
AREVA # 1_410_508_P6 1_410_632_P19 1_417_123_P1 1_410_634_P9 1_410_635_P10 1_410_635_P9 1_410_636_P2 1_410_640_P19 1_410_640_P4 1_410_640_P5 1_410_641_P73 1_410_650_P6 1_410_650_P7 1_410_748_P10 1_410_748_P11 1_410_749_P200 1_410_749_P200 1_410_749_P208 1_410_906 1_412_934_P5 1_413_318_P10 1_413_318_P10 1_413_318_P11
MFR # CR104 1-410-632-P19 E69-30A TSA901 201-J 202-AW 7360K8 IH3-1 WPFS26 GF5352A OR = CLIPFIX35-5 1-410-650-P6 1-410-650-P7 1423123 CC1423 CS8C-22Z-48D CS8C-22Z-48D CS8-P22 1_410_906 1-412-934-P5 6012 6012 S-1
MFR GENERAL ELECTRIC AREVA CHERRY ELECTROMODE STATES STATES CUTLER HAMMER THOMAS & BETTS / RED DOT HUBBELL HUBBELL PHOENIX AREVA AREVA MARATHON MARATHON SPRECHER + SCHUH SPRECHER + SCHUH SPRECHER + SCHUH AREVA AREVA Penn-Union Penn-Union PENN UNION
DESCRIPTION BLOCK CABINET LIGHT DOOR SWITCH ADJUSTABLE THERMOSTAT 45-90F KNIFE SWITCH 1 POLE KNIFE SWITCH 2 POLE PERMISSIVE CONTROL SWITCH RECEPTACLE, ENCLOSURE RECEPTACLE, WEATHERPROOF COVER RECEPTACLE, GFI, 120VAC, 20A END CLAMP FUSE, 15A, CLASS RK5 FUSE, 20A, CLASS RK5 TERMINAL BLOCK 3PT 200A TERMINAL BLOCK COVER CONTROL RELAY 2NO 2NC (48 VDC) CONTROL RELAY 4NO 4NC (48 VDC) AUXILIARY E-TRIP / 69 BLOCK SLUG TERMINAL BLOCK 12PT TERMINAL BLOCK 12PT SHORTING SCREW
024 025 026 027 028 029 030 031 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 048 049
012 001 001 001 007 001 001 001 001 001 001 006 001 001 001 001 002 001 001 001 003 002 001 001 003 004
1_413_318_P3 1_413_652_P1 1_413_653_G8 1_413_999_G3 1_416_091 1_416_206_P4 1_417_056_P1 1_417_125_P1 2_990_024_P2 2_990_035_P1 2_990_156_P2 2_991_268_P1 1_410_508_P1 1_410_748_P1 1_410_748_P1 1_410_748_P3 1_410_651_P2 1_410_651_P3 1_410_651_P2
6006-SCS 1017SP7-A-4-B 700-HT1 17000_0, PCN 265480 1-416-091 1-416-206-P4 1-417-056-P1 GEL 40A15/120V 15199 2-990-024-P2 2-990-035-P1 2-990-156-P2 2-991-268-P1 CR104PBG10B1 TB206 TB206 TB207 RF30A2SP1 RF30A1SP1 RF30A2SP1 GROUND_BAR 6012 6012 1-417-294-G8 MBS 25 49.102.110-16 49.105.100-01
PENN UNION KANSON ALLEN-BRADLEY CHROMALOX AREVA AREVA AREVA GE WIKA AREVA AREVA AREVA GENERAL ELECTRIC BUSSMANN BUSSMANN BUSSMANN MARATHON MARATHON MARATHON AREVA Penn-Union Penn-Union AREVA AEG AREVA AREVA
TERMINAL BLOCK 6PT, SHORTING TIME DELAY RELAY, 2 FORM "C", 48V, 1.5-120 CYC TIME DELAY RELAY, 2 FORM "C", 48VDC ANTICONDENSATION HEATER ASSY 240VAC COPPER STRAP TERMINAL BLOCK COVER AUX 6PT SWITCH BRACKET LIGHT BULB 40W 120VAC DENSITY MONITOR (67,52,48) PSIG-BAR SCALE-PURE SF6 MECHANISM DT72.5 RELAY 6PT TB MOUNTING STRIP-NEW PUSHBUTTON, BLACK, 2NO AUX. TERMINAL BLOCK, 6 PT AUX. TERMINAL BLOCK, 6 PT AUX. TERMINAL BLOCK, 7 PT FUSED KNIFE SWITCH 2 POLE, 15A FUSED KNIFE SWITCH 1 POLE, 20A FUSED KNIFE SWITCH 2 POLE, 20A/SLUG GROUND BAR, 24PT TERMINAL BLOCK 12PT TERMINAL BLOCK 12PT SPRING CHARGE MOTOR FOR FK3-1/131 THERMAL OVERLOAD 10-16A COIL (48 VDC) AUXILIARY SWITCH FK3-X
1_413_318_P10 1_413_318_P10 1_417_294_G8 1_966_957 49.102.110-16 49.105.100-01
D
DEVICE ID EE L1 LS1 TH1 FU4 FU1, FU2, FU3, SW1 LA1 PL1, TH1 PL1 PL1 END5, END6 FU1, FU1, FU3, FU3 FU2, FU4 TBAC TBAC ES EA EA LA1 FU2 TB1, TB2, TB3 TB4 2X, 2X, 2X, 2Y, 2Y, 1X, 2Y, 3X, 3X, 3X, 3Y, 3Y 1X, 3Y, 4X, 4X, 4X, 4Y, 4Y, 1X, 4Y, 5X, 5X, 5X 5Y, 5Y, 5Y, 6X, 6X, 6X, 6Y, 6Y, 6Y, 1Y, 1Y, 1Y 1Y, 2X, 2Y, 3X, 3Y, 4X, 4Y, 5X, 1X, 5Y, 6X, 6Y RE EML H1 FU1, FU1, FU2, FU2, FU3, FU3, FU4 25 LS1 L1 EGA PAN28 PAN29 PAN25, PAN27, PAN30, PAN31, PAN32, PAN33 EE AT1 HT1 AT2 FU1, FU3 FU4 FU2 GND1 TB5, TB6, TB7 TB10, TB9 M1 DT1 MC, MD, ME MA1, MA2, MA3, MB1
1
2
3
3
4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
BILL OF MATERIAL
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
9
OF
13
A
B
C
D BCT WIRING
1
1
3
2
X1
X1 X2 X3
1X
2X
X4
X2
X3
X3
X5 X1
X1
X3
1Y
2Y
X4
4X
X2
X2
X3
X3
4Y
X4 X5
X3
X3
6X
X3 X4
X5
X5
X1
X1
X1
X2
X2 X3
X5
6Y
X3 X4
X5
X5
2 POLE 1
2X 2X1 2X2 2X3 2X4 2X5 GND
1X 1X1 1X2 1X3 1X4 1X5 GND
1X-X1 1X-X2 1X-X3 1X-X4 1X-X5 GND
2Y-X1 2Y-X2 2Y-X3 2Y-X4 2Y-X5 GND
2Y 2Y1 2Y2 2Y3 2Y4 2Y5 GND
1Y 1Y1 1Y2 1Y3 1Y4 1Y5 GND
1Y-X1 1Y-X2 1Y-X3 1Y-X4 1Y-X5 GND
4X-X1 4X-X2 4X-X3 4X-X4 4X-X5 GND
4X 4X1 4X2 4X3 4X4 4X5 GND
3X 3X1 3X2 3X3 3X4 3X5 GND
3X-X1 3X-X2 3X-X3 3X-X4 3X-X5 GND
4Y-X1 4Y-X2 4Y-X3 4Y-X4 4Y-X5 GND
4Y 4Y1 4Y2 4Y3 4Y4 4Y5 GND
3Y 3Y1 3Y2 3Y3 3Y4 3Y5 GND
3Y-X1 3Y-X2 3Y-X3 3Y-X4 3Y-X5 GND
6X-X1 6X-X2 6X-X3 6X-X4 6X-X5 GND
6X 6X1 6X2 6X3 6X4 6X5 GND
5X 5X1 5X2 5X3 5X4 5X5 GND
5X-X1 5X-X2 5X-X3 5X-X4 5X-X5 GND
6Y-X1 6Y-X2 6Y-X3 6Y-X4 6Y-X5 GND
6Y 6Y1 6Y2 6Y3 6Y4 6Y5 GND
5Y 5Y1 5Y2 5Y3 5Y4 5Y5 GND
5Y-X1 5Y-X2 5Y-X3 5Y-X4 5Y-X5 GND
X2
5Y
X4
X4
X5
5X
X5
X3
2X-X1 2X-X2 2X-X3 2X-X4 2X-X5 GND
X2
X4
X4
3Y
X1 X2
X1
6
X1
X2
X5
X4
X5
3X
X4
X4
X2
X1
X1
X2
X5
5
4
2
CT WIRING NOTES: 1) LEADS TO BE TERMINATED WITH BURNDY TYPE INSULATED "YAEV" LUGS. 2) ALL CT LEADS ARE TO BE SHORTED BEFORE SHIPMENT. IF TERMINAL BLOCKS ARE NOT EQUIPPED WITH INTEGRATED SHORTING BARS - SHORTING TO BE ACCOMPLISHED WITH 10GA GRAY SIS VW1 WIRE JUMPERS. WHT-BLK-GND. (IF LEADS ARE NOT COLOR CODED SHORT THE FIRST LEAD-THE LAST LEAD-GROUND) 3) ALL BCT LEADS ARE 10GA WIRE. 4) ALL GROUND WIRES ARE 10GA GREEN SIS WIRE.
POLE 3
POLE 2
1
BCT NAMEPLATE
X1 X2 X3 X4 X5
RATIO: 1200:5 MR ACC: C400 FREQ: 60 Hz RF: 2.0 3 4 PART No.: 1-417-048-N10014 POS: 1X~6X, 1Y~6Y X2-X3 100:5 5 6 X1-X2 200:5 X1-X3 300:5 X4-X5 400:5 CT MFG: NARAYAN X3-X4 500:5 X2-X4 600:5 BUSHING 1 2 3 4 5 6 X1-X4 800:5 UPPER X X X X X X X3-X5 900:5 LOWER Y Y Y Y Y Y X2-X5 1000:5 X1-X5 1200:5 1
3
4
3
2
BCT NAMEPLATE NOTES: 1) NAMEPLATE MATERIAL: ALUMINUM 2) NAMEPLATE LOCATION: INTERNAL 3) NAMEPLATE DIMENSIONS AS SHOWN ON AREVA DRAWING 1_416_218_P3/4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
BCT WIRING
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
10
OF
13
A
B
C
D
SF6 GAS SCHEMATIC POLE A
POLE B
POLE C
RATINGS NAMEPLATE
1
1
TYPE: WIKA DENSITY MONITOR
DT1-72.5 F1 FK CUSTOMER P.O.: ORDER NUMBER: XXXX-DT09 INSTRUCTION BOOK No.: PARTS LIST No.: WIRING DIAGRAM:
SERIAL NUMBER:
POLE ISOLATION VALVE
MANUFACTURE DATE: RATED MAXIMUM VOLTAGE
RATED INTERRUPTING TIME 72.5 kV
RATED VOLTAGE RANGE FACTOR (K) 1.0
RATED SHORT CIRCUIT CURRENT -TERMINAL FAULT
31.5 kA
RATED FREQUENCY
1/4" NPT
FILL VALVE
FILL HOSE AND REGULATOR DETAIL
1) WHEN TESTING THE WIKA DENSITY MONITOR, VALVE NUTS FOR ALL 3 POLES MUST BE LOOSENED 2) PRESS DILO VALVE TO RELEASE GAS DURING TESTING LOOSEN RELEASE VALVE NUTS 5.0 mm CAUTION: DO NOT LOOSEN MORE THAN 5.0 mm
-LOW PRESSURE ALARM
47.9 psig
31.5 kA
GAS PRESSURE REGULATOR WITH PRESSURE GAUGE
29 lb TEMPERATURE RANGE
-OVERVOLTAGE FACTOR -VOLTAGE FACTOR -LINE CHARGING -ISOLATED BANK -BACK-TO-BACK -INRUSH PEAK
SHORT TIME CURRENT DURATION
2.0 1.5 100 A 630 A 630 A 25 kA
-40˚C to +40˚C 3s
7.875 kA
FILL HOSE
FK3-1/131 SPRING CONTROL VOLTAGE -CLOSING
FULL WAVE IMPULSE WITHSTAND 350 kV SWITCHING IMPULSE WITHSTAND
OUT-OF-PHASE SWITCHING
3677 lb MECHANISM TYPE
% DC COMPONENT
3360 Hz
COUPLING SF6 BOTTLE
DILO COUPLING DN8
TOTAL WEIGHT
1200 A CAPACITANCE CURRENT SWITCHING
-INRUSH FREQUENCY
-TERMINAL-TO-GROUND -TERMINAL-TO-TERMINAL
-TRIPPING (EACH) -MOTOR
N/A -SPACE HEATER N/A
AREVA T&D INC., HIGH VOLTAGE SWITCHGEAR ONE POWER LANE - CHARLEROI, PA 15022
POLE ISOLATION VALVE
2
WEIGHT OF GAS
RATED CONTINUOUS CURRENT 3-WAY BALL TEST VALVE
POLE ISOLATION VALVE DETAIL
-NORMAL OPERATING PRESSURE 66.7 psig
-MINIMUM PRESSURE
O-0.3s-CO-15s-CO MANIFOLD
SF6 PRESSURE (@ 20˚C / 68˚F) RELATIVE PRESSURE
52.2 psig 60 Hz -90% SLF WITH 0nFL_g CAPACITANCE (WITHIN 100m)
DUTY CYCLE
2
3.0 CYCLES
72288 CX05070 DT09FK-IM DT09A2242 DT09C02242
48VDC, 8.57A 48VDC, 8.57A 120VAC, 1.6kW 240VAC, 190 W
MADE IN THE USA
VALVE NUT
3
3
66.7 psig - NORMAL 52.2 psig - ALARM 47.9 psig - LOCKOUT AREVA GAUGE No. 2_990_024-P2 RATINGS NAMEPLATE NOTES 1) NAMEPLATE MATERIAL: ALUMINUM 2) NAMEPLATE MOUNTED: EXTERNALLY 3) NAMEPLATE DIMENSIONS AS SHOWN ON AREVA FABRICATION DRAWING 1_416_218_P1/P2 4) MANUFACTURE DATE AND SERIAL NUMBERS TO BE FILLED IN PRIOR TO ENGRAVING
NOTES: 1) ALL TUBING IS 3/8" STAINLESS. 2) GAS SAMPLING CAN BE DONE THROUGH FILL VALVE. 3) POLE ISOLATION VALVES USED TO ISOLATE TANK FROM GAS PIPING. 4) PRESSURE SWITCHES ARE LOCATED INSIDE THE DENSITY GAUGE HOUSING
4
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
GAS SCHEMATIC/RATING PLATE
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
11
OF
13
A
B
C
D
TERMINAL BLOCK MARKER STRIPS DEVICE TAGS
1
M1
MB1
MC
MD
ME
88
88LS
52CC
52TC1
52TC2
AT1
TH1
AT2
DT1
EA
49
LS1
L1
H1
40 W
2X 95 W
ES
FU1
SW1
EML
63GX1
52Y
15A
30 AMP
88F
FU2
FU3
PL1
MA1
MA2
MA3
FU4
RE
20A/SLUG
15A
GFI
52-1
52-2
52-3
20A
79X
TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB9 TB10 1 7 13 28 51 63 75 99 111
HT1
1 2
7R
17
29
52
64
76
100 112
1A
8
18
30
53
65
77
101 113
2A
9
19
31
54
66
78
102 114
1B
9R
20
32
55
67
79
103 115
1X1 1Y1 2X1 2Y1 3X1 3Y1 4X1 4Y1 5X1 5Y1 6X1 6Y1
2B
9A
21
33
56
68
80
104 116
1X2 1Y2 2X2 2Y2 3X2 3Y2 4X2 4Y2 5X2 5Y2 6X2 6Y2
3
9AR 22
34
57
69
81
105 117
1X3 1Y3 2X3 2Y3 3X3 3Y3 4X3 4Y3 5X3 5Y3 6X3 6Y3
4
10
23
35
58
70
82
106 118
1X4 1Y4 2X4 2Y4 3X4 3Y4 4X4 4Y4 5X4 5Y4 6X4 6Y4
5
10A
24
36
59
71
83
107 119 40
1X5 1Y5 2X5 2Y5 3X5 3Y5 4X5 4Y5 5X5 5Y5 6X5 6Y5
6
11
25
37
60
72
84
108 120
1X
DEVICE TAG NOTES: 1) TAG MATERIAL: PLASTIC - YELLOW WITH BLACK LETTERS 2) TAG DIMENSIONS AS SHOWN ON AREVA FABRICATION DRAWING 1_417_376_P1
1Y
2X
2Y
3X
3Y
4X
4Y
5X
5Y
6X
6Y
2
2
EE 52T1
LA1 - 69
E-TRIP
LOCKOUT 59 mm
RESET 3
COLOR - RED W/ WHITE TEXT
TBAC
41
COLOR - BLACK W/ WHITE TEXT
GND GND GND GND GND GND GND GND GND GND GND GND
B1
P12 P12 P12 P12 P12 P12 P12 P12 P12 P12 P12 P12
B2 B3 27 39 62 74 86 110 122 P11 P11 P11 P11 P11 P11 P11 P11 P11 P10
11A
26
38
61
73
85
109 121
3
48 mm
42
DEVICE TAG NOTES: 1) TAG MATERIAL: PLASTIC 2) TAG DIMENSIONS AND COLOR AS SHOWN ABOVE
TERMINAL MARKER STRIP NOTES: 1) STRIP MATERIAL: PLASTIC - YELLOW WITH BLACK LETTERS 2) STRIP DIMENSIONS AS SHOWN ON AREVA FABRICATION DRAWING 1_417_376_P... (SEE P#'S FOR EACH STRIP)
4
TERMINAL MARKER STRIP NOTES: 1) STRIP MATERIAL: PLASTIC - BLACK WITH WHITE LETTERS 2) STRIP DIMENSIONS AS SHOWN ON AREVA FABRICATION DRAWING 1_417_376_P... (SEE P#'S FOR EACH STRIP)
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
TAGS
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
12
OF
13
A
B
C
31.18 792
D
20.67 525
.875 22
1
10.04 255
1
2
2
1.75 44
1.62 41
1.75 44
BOLT CIRCLE 8.86" DIAMETER 225mm
.56 TYP 4 PLACES 14
11.77 299
8 203
1.35 34
1.75 44
1.75 44
1.13 29
1.62 41
.56 TYP 4 PLACES 14
TOP OF TERMINAL CONNECTION AREA
CL
BOTTOM OF TERMINAL CONNECTION AREA
3
MATERIAL: PORCELAIN STRIKE DISTANCE: 643 mm / 25.3 in. CREEPAGE DISTANCE: 1891 mm / 74. in. BIL: 350 kV COLOR: GRAY HIGH VOLTAGE CONNECTION: ALUMINUM - NEMA 4 - THRU HOLE TOP CAP PLATING: NONE
BOTH SURFACES FINISHED FOR USE AS CONNECTION POINT
4
3
BUSHING DATA
CUSTOMER: CITY OF OCALA, FL CUSTOMER ORDER No.: 72288 SUBSTATION: SHARPES FERRY SERIAL No.: 14475A-DT09, 14475B-DT09 2 1 REV.
Updated number of shorting screws for BCT terminal blocks. Changed motot circuit voltage to 120VAC DESCRIPTION
BUSHING OUTLINE
A
AREVA JOB # J14475
4
W.Holt W.Holt DRAWN
A.Izvorean A.Izvorean CHECKED
06/15/09 05/04/09 DATE
A.Izvorean
G.Muchesko
04/20/09
AREVA T&D Inc.
DRAWN
CHECKED
DATE
One Power Lane Charleroi, PA 15022
B
AREVA ORDER # CX05070
CUSTOMER EQ. No.:
C
DRAWING No.:
DT09C02242
SHT
D
13
OF
13
UNCONTROLLED
GRID PRODUCTS Circuit Breakers
12/18 Month Warranty Statement
For ALSTOM GRID, INC. Dead Tank Breakers
Warranty - We warrant, to the original purchaser, only, that the equipment supplied under this contract will conform to the description thereof as contained in our offer, and there are no other warranties, express or implied, which extend beyond the said description, nor any such warranties of fitness for any particular purpose or of merchantability. Such express warranty is given on behalf of the seller only, and is expressly in lieu of an excludes and supersedes any warranty of merchantability or fitness for any particular purpose, and all other warranties, express or implied from any other person or entity including the manufacturer or any subcontractor. In accordance with this warranty, we will correct either by repair, or by the supply of a replacement part, or compensate therefore by equitable adjustment of the contract price, at our sole option, any defect which may be disclosed after delivery or during proper use of the equipment, and which is due solely to faulty design, materials or workmanship not in accordance with the said description; provided, however, that the purchaser gives us written notice of such defect promptly after it is discovered or within a reasonable time after It should have been discovered, and in any event, not later than twelve (12) months after installation, or eighteen (18) months after delivery, whichever occurs later. If such notice of defect is not so given, our obligation to correct such defect or breach of warranty, and constitutes our entire liability, and neither we, the manufacturer nor the subcontractor or their employees or agents shall be liable for any injury, loss or damage whatsoever, which the purchaser may suffer or incur by reason of any such defect or of the necessity of correcting the same, whether a claim is based on breach of contract, negligence, strict tort or any other legal theory. In no event shall we be liable, nor shall the manufacturer or any subcontractor or their employees or agents be liable, in connection with a claim based on a breach of warranty as described in the above paragraph or any other duty or warranty contained in any other paragraph or provision of this contract, for any special, incidental, or consequential damages, based upon breach of warranty, breach of contract, negligence, strict tort or any other legal theory. Such exclusion shall include, but is not limited to, loss of profits, loss of savings, or revenue, loss of use of any equipment, facilities, or services, injury to persons, downtime, and all claims of third parties, (whether such third-party claims are for personal injury or loss to property). However, we will indemnify the purchaser against direct damage or injury to the purchaser’s property or to persons of others which is caused solely by the active negligence of our representatives while at the site of equipment installation for the purpose of the contract, up to the sum of contract value.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
GRID PRODUCTS Circuit Breakers
Exceptions and Clarifications to Special and General and Conditions Dated 02/27/2009 between City of Ocala and ALSTOM Grid, Inc.
The special and general and conditions included in the Request for proposal for this project, which are referenced in this quotation, are hereby accepted by ALSTOM Grid, Inc. subject to the following clarifications and exceptions which shall prevail in the event of discrepancy. 1. Limitation of Liability: Notwithstanding anything to the contrary in the contract documents but to the extent permitted by law Seller shall not in any circumstances under any legal theory, whether based on contract, warranty, tort (including negligence), strict liability, indemnity, professional liability or otherwise, be liable to indemnify the loss of use, loss of production, loss of profits, loss of contracts, loss of data, cost of capital, replacement power, claims of Buyer's Buyers, or any other financial or economic loss or any special, incidental, punitive, indirect or consequential loss or damage whatsoever whether suffered by the Buyer or by any third party. If the Seller fails to deliver the products in accordance with the contract schedule, Seller shall pay to the City of Ocala liquidated damages at a rate of 1% of the price of the delayed products per full week of delay, not to exceed 5% of the price of such delayed products. Liquidated damages shall be the Seller’s exclusive liability and the City of Ocala’s exclusive remedy for delayed performance, provided however that the City of Ocala may terminate this contract or exercise any other remedies set forth herein or otherwise provided by law once the maximum amount of liquidated damages has been reached. The parties agree that such amounts are a reasonable pre-estimate of the damages the City of Ocala will suffer as a result of delay based on circumstances existing at the time the contract was formed and are to be assessed as liquidated damages and not as a penalty. 2. Warranty: The Seller warrants that services will be performed in accordance with good standard practice and products shall be free from defect in design, material and workmanship. The contract warranty period shall be twelve (12) months from the product's commissioning or eighteen (18) months from shipment, whichever is shorter. During the warranty period, the Seller shall re-perform, repair or, at its sole discretion, replace any defective products or parts thereof at its own costs. Buyer shall be responsible for accessing, dismantling and reinstalling the products at its risks and costs. This warranty is exclusive of any other warranty whether express, implied, statutory or otherwise including the warranty of merchantability and fitness for a particular purpose. Seller's liabilities and Buyer's remedies in respect of defects in the products or services and any damage to the products however caused are solely and exclusively as stated in this clause and Seller shall have no liability of any kind for any such defects or damage which appears after expiry of the warranty period described above. 3. Approval of drawings and other documents: Whenever the Buyer must approve drawings or other documents, the Buyer shall approve or comment on those documents within fifteen (15) days of the receipt thereof. 4. Acceptance of the products: The products shall be deemed accepted unless rejected within 30 days of the delivery thereof. 5. Waiver of anticipatory breach remedy: The Buyer hereby waives its right to terminate the contract based on the concept of anticipatory breach except in the event the Seller abandons or notifies the Buyer of its intention to abandon the performance of this Agreement.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
March 16, 2012
FL-USC-12449/1
Page 2
6. Termination for cause: Except in the event the Seller becomes insolvent or bankrupt, commences or has commenced against it any insolvency or bankruptcy proceeding, finds its affairs placed in the hands of a receiver, trustee, or assignee for the benefit of creditors, the Buyer shall not terminate this contract for cause unless the Seller fails to initiate and pursue actions to cure such breach diligently upon written notice from the Buyer. 7. Termination for convenience: If the General and conditions allow the Buyer to terminate the contract for convenience, Buyer shall pay to Seller amounts owed at the time of termination and reimburse the Seller for reasonable costs and expenses incurred (i) in performing the agreement up to the date of termination and (ii) as a result of the termination.
8. Jurisdiction and Venue. The Parties acknowledge that a majority of the negotiations, anticipated performance and execution of this Agreement occurred or shall occur in Marion County, Florida. Any civil action or legal proceeding arising out of or relating to this Agreement shall be brought only in the United States District Court, Middle District of Florida, Ocala Division. Each party consents to the exclusive jurisdiction of such court in any such civil action or legal proceeding and waives any objection to the laying of venue of any such civil action or legal proceeding in such court or the right to bring an action or proceeding in any other court. Service of any court paper may be affected on such party by mail, as provided in this Agreement, or in such other manner as may be provided under applicable laws, rules of procedures or local rules. 9. Jury Waiver. In any civil action, counterclaim, or proceeding, whether at law or in equity, which arises out of, concerns, or relates to this Agreement, any and all transactions contemplated hereunder, the performance hereof, or the relationship created hereby, whether sounding in contract, tort, strict liability, or otherwise, trial shall be to a court of competent jurisdiction and not to a jury, Each party hereby irrevocably waives any right it may have to a trial by jury. Any party may file an original counterpart or a copy of this Agreement with any court, as written evidence of the consent of the parties hereto of the waiver of their right to trial by jury. Neither party has made or relied upon any oral representations to or by any other party regarding the enforceability of this provision. Each party has read and understands the effect of this jury waiver provision. 10. Confidentiality-Ownership: All designs, drawings and other technical information relating to the products and services provided by the Seller under this Agreement, and the intellectual property rights therein made or acquired by the Seller prior to or during the performance of this Agreement shall be and remain the property of the Seller. Such technical information shall be kept confidential by the Buyer and shall not be used by Buyer otherwise than for the purposes of the operation and maintenance of the products. 11. Suspension by Seller: Suspension: If Buyer fails to make any payment when due or perform on time any of its other obligations under this Contract and without prejudice to any other rights or remedies: (i) Seller shall be entitled to suspend performance of the Agreement until the failure is remedied, (ii) the time for performance of the Agreement by Seller shall be extended accordingly, (iii) any cost (including financial costs and storage, demurrage or other charges) thereby incurred by Seller shall be paid by Buyer. Seller may terminate this Contract if the suspension exceeds three (3) months. In such event, the Seller shall be entitled to the payment of (i) sums due (ii) costs incurred in the performance of the Contract up to the date of termination and not already paid and (ii) costs incurred as a result of termination. 12. Insurance: Insurance coverage to be agreed upon.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com
March 16, 2012
FL-USC-12449/1
Page 3
13. Miscellaneous: 13.1 If (i) Buyer refuses to confirm that it will take delivery of the product in accordance with the of this contract, (ii) does not take delivery of the product within 30 (thirty) days of notification that the product is ready for delivery (iii) postpones the date of delivery of the product without the prior written consent of Seller or (iv) suspend performance of the contract without the consent of the Seller, after completion of manufacture and testing of the Product or for a period exceeding in the aggregate three (3) months, and without prejudice to any other right or obligation that the Seller may have under the Contract, at law or in equity, the Seller will be entitled to compete the manufacture of the product and may store the Product at the risks and costs of the Buyer. In such instance, title to the Product shall to the Buyer and Seller shall be entitled to payment of the contract price corresponding to the shipment and/or delivery of the Product. 13.2 Notwithstanding any provisions of any applicable laws including common law, any additional or different and conditions set forth in Buyer's purchase order are objected to by ALSTOM Grid, Inc. and will not be binding upon ALSTOM Grid, Inc. unless specifically assented to in writing by an authorized representative of ALSTOM Grid, Inc." 13.3 Buyer's purchase order shall constitute an acceptance of the quotation or proposal of ALSTOM Grid, Inc. even if the purchase order provides otherwise and/or does not reference the ALSTOM Grid, Inc. quotation or proposal. To the extent permitted by law, the so-called "knock out" rule, in which differing between an offer and acceptance are knocked out and are not deemed part of the resulting contract between the parties, shall not apply to this contract." 13.4 Notwithstanding anything to the contrary, the quotation of Seller for this project which include these exceptions and clarifications shall take precedence over any other documents including the Request for proposal documents. 13.5 Any right to set off sums owed to the Seller, if any, shall be restricted to sums owed by either party to the other one under this contract.
Alstom Grid, Inc. One Power Lane Charleroi, PA 15022 Phone: 724-483-7308 Fax: 724-483-7771 www.alstom.com