http://www.sea-plus.co.kr
Fire Fighting Systems and Equipments
Fire Fighting Systems and Equipments
Go with
SEAPLUS for your safety of fire extinguishing systems,
equipments, and others
Go with
SEAPLUS for your safety life - 2Page
SEAPLUS f o r
your safety of fire extinguishing systems, equipments, and others
Fire Fighting Systems and Equipments
Index Introduction Company history External fire fighting system Water mist fire extinguishing system High expansion foam fire extinguishing system Deck foam fire extinguishing system High pressure CO2 fire extinguishing system Low pressure CO2 fire extinguishing system Dry chemical powder fire extinguishing system Automatic sprinkler fire extinguishing system Fire detection & alarm system Loose fire fighting equipment Quality certification Total fire test shop World wide a/s net work Plant project team
04Page 05Page 06~07Page 08~09Page 10Page 11Page 12Page 13Page 14Page 15Page 16Page 17Page 18Page 19Page 20~21Page 22~23Page
SEAPLUS for your safety life - 3Page
GO with SEAPLUS for your safety of fire extinguishing systems and equipments.
SEAPLUS for your safety life - 4Page
SEAPLUS for your safety life
Introduction SEAPLUS CO., LTD. is one of leaders and manufacturers for fire fighting systems & safety equipment in Korea and we have taken our expertise & experience into the world wide market to establish a reputation for excellence and customer . We are confident that you will find our presentation of interest and assure you of our competence and desire to realize your contract in away totally satisfactory to you, our prospective client.
Company history 1994 1997 1999 1999 2000 2001 2001 2002 2002 2002
7 4 7 9 4 4 6 5 6 7
2003 2004 2006
9 12 10
2006 2007 2007 2008 2008 2008 2008 2008
12 8 10 7 7 10 11 12
Established DAE KYEONG Engineering Co. Incorporated as "SEAPLUS CO., LTD." Acquisition for license of Fire protection system construction by Busan city Certified ISO 9001 by KOREAN of SHIPPING Moved the factory & office to NOKSAN industrial complex Technical R & D Lab. Approved by KITA Established Total fire test shop Designated as Venture Business Developed Local fire fighting system in According with MSC Circ.913 Certified as technology-innovating SME (INNO-BIZ) business by Small & Medium Business istration Awarded Presidential citation Awarded Advance Idea Man (New Knowledge Man) Developed Total Application Water mist fire extinguishing system in According with MSC Circ.1165 Selected as "Leading Enterprise in Strategic Industry" by Busan city Chosen as Promising Enterprise by WOORI BANK Developed Self-rotation type high expansion foam generator Established 2nd manufacturing factory Superiority Business man Awarding by Busan city Awarded the Prime Minister Acquisition for license of Fire protection system design by Busan city Awarded "Commendation for Genuine S/W " by Minister of Culture, Sports and Tourism SEAPLUS for your safety life - 5Page
SEAPLUS for your safety life
In fire fighting system, the external fire fighting system is to extinguish and suppress fires against external vessel. It is equipped with fire monitor, fire fighting pump, electric motor, portable controller and fire monitor and so on. Fire fighting pump can be driven by transmission power from driven-engine or dedicated motor. According to mounting location of fire monitor, there are sliding tower, folding tower and platform on wheel house. Tower's characteristic is to be folded and storaged in a low and compact size. It would significant facilitate handling on fire suppression and extinguishing using dual monitor of foam liquid and dry powder.
External Fire Fighting System Water monitor system capacity
(ABS Rule 5-9-1/Table.1, 2006) Class
Class Notation Number of water monitors Discharge rate per monitor, m /h 3
Number of pumps
Class
Class
2
3
4
4
1,200
2,400
1,800
2,400
1-2
2-4
2-4
2,400
7,200
9,600
Monitor range, m
120
150
150
Height, monitor, m
45
70
70
Number of hose connection each side of vessel
4
8
10
Number of fireman's outfits
4
8
10
Fuel oil capacity
24
96
96
Total capacity, m3/h
1) Range : measured horizontally from the monitor outlet to the mean impact area. 2) Height : minimum height of the trajectory of water monitor jet measured vertically from sea level assuming a mean impact area located at a horizontal distance not less than 70m from the nearest part of the fire fighting vessel. 3) Fuel oil capacity is to include provisions for continuous operation of all monitors in addition to the total capacity of the vessel's fuel oil tanks required for continuous fire fighting operation. See also 5-9-2/5.
Controller
SEAPLUS for your safety life - 6Page
Fire Pump Unit
Model FE-65 FE-80 FE-100 FE-125 FE-150 FE-200 FE-200D SFE-200 SFE-200S SFE-200D SFE-200DS FEH-200 FEH-200D FEH-250 FEH-300
Capacity L/min
m3/h
500 ~ 1,500 1,500 ~ 3,000 3,000 ~ 5,000 5,000 ~ 8,000 8,000 ~ 11,333
30 ~ 90 90 ~ 180 180 ~ 300 300 ~ 480 480 ~ 680
11,333 ~ 20,000
680 ~ 1,200
11,333 ~ 25,000
680 ~ 1,500
25,000 ~ 40,000 40,000 ~ 60,000
1,500 ~ 2,400 2,400 ~ 3,600
Actuating Method Electric Electric Electric Electric Electric Electric Electric Electric Electric Electric Electric Electro-Hydraulic Electro-Hydraulic Electro-Hydraulic Electro-Hydraulic
Remark
Double Gun
Double Gun Double Gun Double Gun
Discharge of Fire Monitor
Sliding Tower
Portable Controller Folding Tower
SEAPLUS for your safety life - 7Page
SEAPLUS for your safety life
Using spraying water in all fires, the water mist system is to suppress and fight all fires in protected areas. In this fire extinguishing system, water is sprayed in high or low pressure to make small water droplets. Using water droplets, vaporization effect gets increased as much as surface area expansion. Water mist is sprayed into flame so that to promote vaporization and decrease in oxygen concentration as suffocation. Extinguishing effect becomes increased by cooling. The system has two types of local fire fighting system and total fire fighting system. Especially, in case of local application, it is designed and installed to cover main engine, aux. engine, boiler, incinerator and purifiers as protected area respectively. The arrangements of nozzle will be provided according to capacity of nozzle in relevant protected area. In case UMA, after fire happens, using fire alarm system by detecting fire automatically, water mist pump shall be runned. And water is discharged into fire area through nozzle to extinguish it. During spraying water, audible and visible alarms are provided in the protected space.
Water Mist Fire Extinguishing System
Water Mist Controller
Water Mist Skid(Low)
Water Mist Controller
Water Mist Skid(High)
SEAPLUS for your safety life - 8Page
Local Operating Box
Local Application System Model : SPF-1 Installation (m)
Working Pressure (bar)
K-Factor (Flow rate)
Spacing
50 ~ 60
1.5 (10.6~11.6LPM)
1.5
0.6
3.0
Vertical Downward
90 ~ 100
1.5 (14.2~15.0LPM)
2.5
3.0
8.0
Vertical Downward
Working Pressure (bar)
K-Factor (Flow rate)
Spacing
40 ~ 90
1.65 (10.6~44LPM)
4.0
Working Pressure (bar)
K-Factor (Flow rate)
Projection
Min. Height Max. Height
Model : HSN-510 Installation (m)
Projection
Min. Height Max. Height
0.6
3.0
Vertical Downward
Model : SPF-3
Min. 7.5
4.76 (13LPM)
Installation (m) Spacing
Projection
Min. Height Max. Height
4.0
0.5
17.0
Vertical Downward Inclined angle (30~60 form vertical)
8.0
0.5
5.0
Side Shooting
Total Application System Model : SPF-1C (Accomodation) Installation (m)
Working Pressure (bar)
K-Factor (Flow rate)
Spacing
50 ~ 60
1.5 (10.6~11.6LPM)
1.5
0.6
3.0
Vertical Downward
90 ~ 100
1.5 (14.2~15.0LPM)
2.5
3.0
8.0
Vertical Downward
Projection
Min. Height Max. Height
Model : SPF-2 (Engine Room) Nozzle
Model
Working K-Factor Pressure (bar) (Flow rate)
Celling nozzle SPF-2 Bilge nozzle SPF-2 Doorway nozzle SPF-2D
Installation (m) Spacing
Location
Max. distance to wall
0.46 (3.56LPM) 4.0 4.0 Max. 1.5 below Celling 60
0.46 (3.56LPM) 3.2 3.2
Bilge plate mounted
0.21 (1.62LPM) 0.4(tip to tip) Max. 0.3 Above Doorway
Projection
2.0 -
Vertical Downward
-
SEAPLUS for your safety life -9Page
SEAPLUS
for your safety life
High Expansion Foam Fire extinguishing system High expansion foam system is used as alternative system of Halon extinguishing system. As halon replacement being phased out due to environmental reasons, high expansion foam system is good replacement. It is also excellent alternative system of CO2 and sprinkler systems. High expansion foam system is suitable for installation in engine room together with adjacent spaces as local and /or total flooding. The system is manually operated but may be supplied upon request with remote operation. High expansion foam system has been extensively full scale tested for fires in machinery spaces, class 1, 2&3, following IMO guidelines. High expansion foam system extinguishes fires with a combination of water and foam. Foam fills all the voids and seals the fire from the air supply, and steam absorbs heat energy when water is vaporized. An inert atmosphere is created and the fire is extinguished. When a fire occurs, fire fighting can immediately begin by the of high expansion foam system and there is a further advantage of reduced damage due to the cooling effect created by the water and the foam on surfaces. When installing high expansion foam system there is no need for large air ducts or unnatural hull opening to produce foam. simplified piping system and low weight generators in combination with seaplus traditionally and well proven foam central unit makes the whole system easy to install.
Foam Generator
Certification
Proportioner
High Expansion Foam Generator Model
V : Vertical downward H : Horizontal
Foam Solution Foam Capacity Working Flow rate(LPM) Pressure(Mpa) (m3/min)
Expansion Ratio(Times)
>28
V 880 / H 877
SPHG-30
32
SPHG-60
75
>65
SPHG-90
110
>96
0.4
SPECIFICATION 1) High Expansion Foam Concentrate : Meteor P +, Skum 2) Mixing Ratio : 2% (Foam Concentrate) + 98% (Water) 3) High Expansion Foam Generator
SEAPLUS for your safety life - 10Page
V 877 / H 874 V 874 / H 877
Connection Method JIS10K-25A Flange
K-Factor
Weight (kg)
16.0
4
37.5
7
55.0
10
Deck Foam Fire extinguishing system Foam system for the protection of chemical and oil tank decks or heli-decks in accordance with class requirements and IBC code. Calculated and designed in accordance with international regulations. The foam monitors may be delivered as manually operated (electric or hydraulic type).
Foam Tank Unit
Balanced Pressure mixer
Foam Proportioner Model
Max. Water Flow Rate (LPM)
50F - 100W 50F - 150W 80F - 200W 80F - 250W
3,000 6,000 13,000 20,000
Connection Size Water Side Foam Side JIS10K-100A JIS10K-150A JIS10K-200A JIS10K-250A
JIS10K-50A JIS10K-50A JIS10K-80A JIS10K-80A
Foam Monitor
Foam Hose Box
Model
Capacity (LPM)
Connection Size
FM - 65 FM - 80 FM - 100 FM - 125
500 ~ 1,500 1,500 ~ 3,000 3,000 ~ 5,000 5,000 ~ 8,000
JIS10K-65A JIS10K-80A JIS10K-100A JIS10K-125A
Foam Monitor
SEAPLUS for your safety life - 11Page
SEAPLUS
for your safety life
High Pressure CO2 Fire extinguishing system Carbon Dioxide(CO2) Gas, the fastest and most efficient extinguishing agent against fires in protected spaces, suffocates the fire within designated time and minimize the damage in protected spaces. The Fire Extinguishing System extinguishes the fire by means of CO2 gas. The system consists essentially of CO2 cylinders, main isolating valve(s), manifold, CO2 nozzles in compartment protected space, and pipe lines connecting these main parts. The system is to be designed by the required discharging time, CO2 cylinders quantity and which are stored in a independent CO2 room. For further security in ship's cargo holds, a smoke detection system can be combined with the CO2 system. CO2 gas, the fastest and most efficient extinguishing agent against fires in protected spaces, suffocates the fire within designated time and minimize the damage in protected spaces.
Master Control Cabinet
Cylinder Valve
Pressure Operating Distribution Valve(1”~6”)
SEAPLUS for your safety life - 12Page
Low Pressure CO2 Fire extinguishing system The required quantity of CO2 gas is stored in one or two large tank. The tank unit is furnished with its own refrigeration machinery to keep the temperature and also to adjust the pressure at the correct level. The system is designed and installed so that CO2 gas can be discharged into relevant protected area using valve control cabinet. At that moment, the required quantity of CO2 gas is adjusted by timer which is installed at relevant valve control cabinet.
Instrument Control
Pressure CO2 Storage Tank
Safety Valve
Safety Valve
Double Stop Valve
15~25mm(1/2”~1”)
3~300mm(1/8”~12”)
15~32mm(1/2”~1-1/4”)
Refrigerator
SEAPLUS for your safety life - 13Page
SEAPLUS
for your safety life
Dry Chemical Powder Fire extinguishing system The SEAPLUS dry powder system is designed specifically for marine application so that can be met with SOLAS requirements for LPG and LNG tankers.
Dry Chemical Powder Gun
Pneumatic Control Cabinet
Hose Station Box
Model
Monitor
Hand Hose Gun
SEAPLUS for your safety life - 14Page
Dry Chemical Powder Skid
Flow Rate (kg/sec)
Shooting Length (m)
10
10
16
18
20
23
25
30
3.5
5 ~ 10
Automatic Sprinkler Fire extinguishing system This system is installed in accommodation spaces and other service on the vessels such as enger ships and car ferries. The sprinkler system is the most effective at its early stage in extinguishing fire. Statistics estimates that about 70% of all fires has been extinguishing by less than three sprinkler heads.
Operation of sprinkler-system Immediately after fire breaks out in a protected area, the intense heat rises rapidly under ceiling zone. As soon as the ambient temperature has reached the set release temperature, the glass bulb bursts and the sprinkler is activated. The sprinkler pressure tank contains fresh water, which being discharged into protected area, at a constant pressure level. When sprinkler nozzles are actuated, the sprinkler system is activated resulting in a pressure drop in the sprinkler storage tank. Water supply is provided with adequate pressure by dedicated pump set which is arranged to start automatically when the pressure falls down below set point of the pump's start-up relay. The sea ensures an inexhaustible supply as fire extinguishing agents, posing no threat to enger and crew. For safety reasons, the sprinkler pumps can be operated form the ship's main and emergency switchboard.
Sprinkler Nozzle Release
Sprinkler Heads
Sprinkler Central Nozzle Escutcheons
SEAPLUS for your safety life - 15Page
SEAPLUS for your safety life
The fire detection and alarm system consists of fire detectors, manual call point, control , repeater and alarm device and so on. Upon the receipt of fire and fault signals, fire alarm system shall send relevant signals to alarm monitoring, alarm device and VDR with audible and visible alarm as well as indicate fire and fault signals on LCD of fire alarm with audible alarm.
Fire detection
Alarm system
Fire Alarm Control Panet (JB-QB-4508) -4 Loops / 508 Addressable Detectors Fire Alarm Repeater (JB-QB-4508R) Heat Detector Smoke Detector Infra Red Type Flame Detector Manual Call Point Isolator
Fire Alarm Controller
Flame Detector
Heat Detector
SEAPLUS for your safety life - 16Page
Fire Alarm Repeater
Manual Call Point
Smoke Detector
Isolator
Loose Fire Fighting Equipment Fire Man’s Outfit Equipments
Fire Suit
Air Breathing Apparatus
Fire Axe With Beit and Life Line
Safety Lamp
Fire Extinguisher
9L Foam 6.8kg CO2 6.5kg Dry Powder Fire Extinguisher (Portable Type)
45L Foam 135L Foam Fire Extinguisher (Wheel Type)
Portable Foam Applicator Assembly
Sea water Fire Fighting Equipments
Fire Hose Rack
International Shore Connection
Fire Hose Box
Fire Hose Reel
Fire Hose With Coupling
Jet / Spray Nozzle
Spanner
SEAPLUS for your safety life - 17Page
Quality Certification
SEAPLUS for your safety life - 18Page
SEAPLUS for your safety life
Total Fire Test Shop Scales Specification Length Breadth Height Volume Material Major Zone Division
IMO Circ.668 CLASS III (Above 3,000 m3 for large ship) 35 m 11 m 12 m 3,750 m3 Anti-Fire Block & Anti-Fire Foam Total Fire Test Area : Machinery Area / Control & Monitoring Room
Control & Monitoring System Remote Control for : Monitoring & Recording
O2 Concentration Analysis Equipment
Pump, Valves Agent Flow & Pressure F.O. Flow, Pressure & Temperature Test Shop Atmosphere Temperature Engine Mock-Up Temperature F.O. Spray Nozzle Test Shop Atmosphere All Data Analysis System Data Saving on Computer & Print
What Fi-Fi System can test ?
What Kind of fire can test ?
CO2 System Low Expansion Foam System High Expansion Foam System Dry Chemical Powder System Water Mist System Water Spray System Smoke Sampling System Fire Detection System Sprinkler System Portable Extinguisher Other Water Based Fi-Fi System
Oil Spray Fire
High Pressure (150 bar) Low Pressure (7 bar)
Engine Mock-Up Pool Fire Class A Fire Cabin, Corridor & Public Space Fire (Future)
SEAPLUS for your safety life - 19Page
WORLD WIDE A/S NET WORK SEAPLUS makes the future with the challenge to a new world and unswerving R & D efforts. You shall be assured of our efforts for the world-highest precision and quality.
VIKING LIFE-SAVING EQUIPMENT A/S (HEAD OFFICE) Saedding Ringvej 13 6710 Esbjerg V Denmark : Mr. Jan Nikolaj Jensen TEL : +45 76 118100, FAX : +45 76 118101 [ SEAPLUS share the following world-wide service station with VIKING A/S] USA NORWAY TURKEY FINLAND RUSSIA SWEDEN ESTONIA UAE SPAIN SOUTH AFRICA ICELAND NETHERLANDS BELGIUM ITALY SINGAPORE MALAYSIA DENMARK HONG KONG
SEAPLUS for your safety life - 20Page
- Miami, California, Cape Canaveral, Washington - Montivilliers, Vitrilles - Straume, Oslo, Avladsnes, Alesund - Tuzla/Istanbul - Lieto - Petersburg - Stockholm - Tallinn - Dubai - Cadiz, Puxeiros-Mos-Vigo, Barcelona - Cape Town, Durban - Hafnafjordur - LX Zwijndrecht, El Harlem, Delfzijl - Lokeren - Napoli, La Spezia, Messina - Johor Darul Takzim - Esbjerg - Hamburg, Bremerhaven - Kwai Chung, N.T.
Go with
SEAPLUS f o r
your safety of fire extinguishinh systems, eguipments, and others
CHINA
SINGAPORE
NETHERLAND
OCEAN MARINE SERVICE CO., LTD
W.H BRENNAN & CO PTE. LTD.
MK-MARINE GMBH
No. 1100 Wuzhong Road, Minhang Qi, Shanghai, China
47 Loyang Way, Singapore 508739
: Mr. J.G.Choi TEL : +86 21 5422 4157, FAX : +86 21 5422 4156 E-MAIL :
[email protected]
: Mr. Desmond Goh TEL : +65 6549 5111, FAX : +65 6542 5246 E-MAIL :
[email protected]
Inglasco Fire System B.V, Gounderakstraat 22, 307 DB Rotterdam, Netherlands
HAI CHEUNG TRADING CO. (HK) LTD Shanghai Representative office 8/F, Ju Yang Tower, No. 1200 Pudong Avenue, Shanghai, China, 200135
MK-MARINE GMBH
: Mr. John Fongers TEL : +31 10 479 3611, FAX : +31 10 479 2355 E-MAIL :
[email protected]
U.A.E
: Mr. Gus Hou TEL : +86 21 6888 9889, FAX : +86 21 6329 3888 E-MAIL :
[email protected]
Werner Oltersdorf Westkai 50, D-27572, Bremerhaven,
MAXELL INTERNATIONAL L.L.C
: Mr. Werner Oltersdorf TEL : +49 471 97227 13, FAX : +49 471 97227 27 E-MAIL :
[email protected]
P.O BOX 47620, DUBAI, U.A.E
JAPAN
FIREFLY
PRO-TECH Co.,Ltd.
Am Redder 1 22941 Bargteheide,
1-6, Taisho-cho 6-Chome, 1 mabari, Ehime, 794-0025, Japan
: Mr. Hiroki Kumazawa TEL : +81 898 23 2051, FAX : +81 898 23 2078 E-Mail :
[email protected]
: Mr. N.S. PAI TEL : +971 4 2676128, FAX : +971 4 2676129 E-MAIL :
[email protected]
TURKEY
: Mr. Merijn Struijs GANI SHIP SPARE LTD TEL : +49 (0) 4352 20 48 911, FAX : +49 (0) 4352 20 48 920 Gumussuyu Mah, Kutlu Sok. No. 834437 Taksim Istanbul, Turkey E-MAIL :
[email protected]
TAIWAN PILOT MARINE TECHNOLOGY & ENGINEERING CO.,LTD. No.217, Hsing Sheng Road, Chuan Cheng Dist. Kaohsiung, Taiwan. R.O.C.
: Mr. Johny Wan TEL : +886 7 8211545, FAX : +866 7 8211571 E-MAIL :
[email protected]
SEAPLUS for your safety life - 21Page
SEAPLUS Plant Project Team
DESIGN & CONSTRUCTION for FIRE FIGHTING SYSTEM of PLANT PROJECT Seaplus’s Plant project team consists of specialists for mechanics, electronics, thermodynamics and fluid mechanics based fire fighting system. Plant project team has delivered to all Korean thermal power plant a fire fighting system & fire alarm and fire detection system for parts of bulk material handling system and boiler system after 2003 year. We have licenses for fire fighting design and construction approved by Korean government. We accepted an order for the fire fighting system of Cuba DPP project and the service gas supply system of Bahrain IWPP project recently.
Plant Project Team FIRE FIGHTING SYSTEM - CO2 SYSTEM - DRY CHEMICAL SYSTEM - WATER SPRAY SYSTEM - CLEAN AGENT SYSTEM - SPRINKLER SYSTEM - WATER SPRAY SYSTEM - FOAM SYSTEM - HYDRANT SYSTEM
FIRE ALARM & FIRE DETECTION SYSTEM KDX-III DELUGE & SPRINKLER SYSTEM
SEAPLUS for your safety life -22Page
Seaplus plant project team plans, designs, manufactures and supplies a full range of proprietary products for dust suppression, return belt washing and water spray system. Plusgun dust suppression system consists of the PLC based control system and a shooting gun which spray water on the ground uniformly. Plus dust suppression system is focused on developing intelligent solutions for the flying ash at raw material storage area like as coal, coke and scrap iron etc or inside chute and skirt in transfer tower. Return belt washing system for protect to stack a raw material on the floor in gallery or girder is applied to bulk material handling system.
PLUS GUN DUST SUPPRESSION SYSTEM
PLC BASED CONTROL SYSTEM
WATER SPRAY SYSTEM Water spray system is designed to direct water at a required density, from nozzles having predetermined patterns to completely impinge water onto the hazard surface being protected. It is designed for use in a variety of special hazards applications including flammable and combustible liquid hazards, transformers and turbines.
SERIVCE GAS SUPPLY SYSTEM Service gas system applied to steam power generator. Nitrogen (N2) gas system shall be to blanket the steam and water line in order to prevent corrosion during long term wet lay up. Carbon Dioxide (CO2) gas system is used for purging the air and other gases in pipe system. Hydrogen (H2) gas system is used as a coolant for the main steam turbine or generators.
SEAPLUS for your safety life - 23Page
ADD TEL FAX E-mail
1575-3, SongJeong-Dong GangSeo-gu Busan Korea
Rev. No.
200905 Vol. 1
+82-51-831-0119 +82-51-831-1119
Domestic /
[email protected] http://www.sea-plus.co.kr